INSTALLATION INSTRUCTIONS
Internal Wall Under Floor Installation using 40mm ø PVC Flue.
Note: All flue pipe connections need to be sealed with PVC
cement, except Flue Fan Connection.
Note: Total installation length in 40mm ø PVC pipe 5100mm
with 1 x 90º and 2 x 45º bends.
Caution: To avoid water trap in Flue system 40mm ø PVC pipe
must be supported every 2 metres to avoid PVC pipe
sagging, and PVC pipe must have fall to ground level
(see sketch).
Caution: If a water trap develops in the flue the heater will cease
to operate or could soot up.
18
External Wall
65mm PVC cowl to
suit 40mm PVC flue
pipe.
90º Elbow
90º Elbow
Internal Wall