USER MANUAL
Modbus TCP Interface (710-14812-00D)
5
3.3
Network Connection
Ethernet Ports
The device has two Ethernet ports. If only one connection is required, either port can
be used.
Cables
Use Category 5, 5e, 6 or 6e cable to connect to the device.
EMC Precautions
To minimise electromagnetic interference, Ethernet cables should be separated from
motor and mains cables by 200 mm.
If the Ethernet cable must cross motor or mains cables, the crossing should be at an
angle of 90°.
3.4
Network Establishment
The controller must establish communications directly with each device before the
device can participate in the network.
3.5
Addressing
Each device in a network is addressed using a MAC address and an IP address.
•
The device can be assigned a static IP address during configuration, or can be
configured to accept a dynamic IP address (via DHCP).
•
The MAC address is fixed within the device and is printed on a label on the front of
the device.