USER MANUAL
14
Modbus TCP Interface (710-14812-00D)
Register Description
Bits
Details
30262
Current
0 to 13 Phase 2 current (rms)
14 to 15
Reserved
30263
Current
0 to 13 Phase 3 current (rms)
14 to 15
Reserved
30264
Voltage
0 to 013
Phase 1 voltage, rms
(medium voltage products only)
14 to 15
Reserved
30265
Voltage
0 to 13
Phase 2 voltage, rms
(medium voltage products only)
14 to 15
Reserved
30266
Voltage
0 to 13
Phase 3 voltage, rms
(medium voltage products only)
14 to 15
Reserved
30267
Parameter list
version number
0 to 7
Parameter list minor revision
8 to 15 Parameter list major version
30268
Digital input
state
0 to 15 For all inputs, 0 = open, 1 = closed (shorted)
0 = Start
1 = Stop
2 = Reset
3 = Input A
4 = Input B
5 = Input C, if fitted
6 = Input D, if fitted
7 to 15 =
Reserved
30269~
30281
Reserved