USER MANUAL
Modbus TCP Interface (710-14812-00D)
17
Register Description
Bits
Details
40605
Current
0 to 13 Average rms current across all three phases
14 to 15
Reserved
40606
Current
0 to 9
Current (% motor FLC)
10 to 15
Reserved
40607
Motor temperature 0 to 7
Motor 1 thermal model (%)
8 to 15
Reserved
40608
Power
0 to 11 Power
12 to 13 Power scale
0 = Multiply power by 10 to get W
1 = Multiply power by 100 to get W
2 = Power (kW)
3 = Multiply power by 10 to get kW
14 to 15
Reserved
40609
% Power factor
0 to 7
100% = power factor of 1
8 to 15
Reserved
40610
Voltage
0 to 13 Average rms voltage across all three phases
(medium voltage products only)
14 to 15
Reserved
40611
Current
0 to 13 Phase 1 current (rms)
14 to 15
Reserved
40612
Current
0 to 13 Phase 2 current (rms)
14 to 15
Reserved
40613
Current
0 to 13 Phase 3 current (rms)
14 to 15
Reserved
40614
Voltage
0 to 13 Phase 1 voltage, rms
(medium voltage products only)
14 to 15
Reserved
40615
Voltage
0 to 13 Phase 2 voltage, rms
(medium voltage products only)
14 to 15
Reserved
40616
Voltage
0 to 13 Phase 3 voltage, rms
(medium voltage products only)
14 to 15
Reserved
40617
Parameter list
version number
0 to 7
Parameter list minor revision
8 to 15 Parameter list major version