USER MANUAL
Modbus TCP Interface (710-14812-00D)
11
8.3
Standard Mode
Command and Configuration Registers (Read/Write)
Register Description
Bits
Details
40001
Command
(single write)
0 to 7 To send a command to the starter, write the
required value:
00000000 = Stop
00000001 = Start
00000010 = Reset
00000100 = Quick stop (coast to stop)
00001000 = Forced communication trip
00010000 = Start using Parameter Set 1
1
00100000 = Start using Parameter Set 2
1
01000000 = Local control
10000000 = Remote control
8 to 14
Reserved
15
Must = 1
40002
Reserved
40003
Reserved
40004
Reserved
40005
Reserved
40006
Reserved
40007
Reserved
40008
Reserved
40009
2
Parameter
management
(single/multiple
read or multiple
write)
0 to 15 Manage soft starter programmable parameters
1
Ensure that the programmable input is not set to Motor Set Select before using this
function.
2
Refer to the relevant soft starter literature for a complete parameter list. The first
product parameter is always allocated to register 40009. The last product parameter is
allocated to register 40XXX, where XXX = 008 plus total number of available
parameters in the product. The Modbus TCP protocol limits read/write operations to a
maximum of 123 registers at one time. The registers must be consecutive. These
registers support multiple write (Modbus function code 16). Attempting to write to a
single register will return an error code 01 (Illegal function code).