USER MANUAL
12
Modbus TCP Interface (710-14812-00D)
Status Reporting Registers (Read Only)
NOTE
For models EMX3-0053B and smaller, current reported via communications is
10 times greater than the actual value (displayed on the keypad).
Register Description
Bits
Details
30240
Starter state
0 to 3
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including temperature
check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
4
1 = Positive phase sequence
(only valid if bit 6 = 1)
5
1 = Current exceeds FLC
6
0 = Uninitialised
1 = Initialised
7 to 15
Reserved
30241
Trip code
0 to 7
Refer to
Trip Codes
on page 19.
8 to 15
Reserved
30242
Motor current
0 to 7
Average 3-phase motor current (A)
8 to 15
Reserved
30243
Motor
temperature
0 to 7
Motor 1 thermal model (%)
8 to 15
Reserved
30244 ~
30249
Reserved
30250
Version
0 to 5
Reserved
6 to 8
Product parameter list version
9 to 15 Product type code:
4 = CSX
6 = EMX3
11 = MV
30251
Model number
0 to 7
Reserved
8 to 15 Soft starter model ID
30252
Reserved
30253
Reserved