Modbus TCP Interface (710-14812-00D)
Register Description
Bits
Details
40005
Motor current
0 to 7
Average 3-phase motor current (A)
8 to 15
Reserved
40006
Motor temperature 0 to 7
Motor 1 thermal model (%)
8 to 15
Reserved
40007
Reserved
40008
Reserved
40009
1
~
40200
Parameter
management
(single/multiple
read or multiple
write)
0 to 7
Manage soft starter programmable
parameters
8 to 15
Reserved
40600
Version
0 to 5
Binary protocol version
6 to 8
Parameter list version number
9 to 15 Product type code:
4 = CSX
6 = EMX3
11 = MV
40601
Reserved
40602
Reserved
40603
Reserved
40604
Starter state
0 to 4
0 =
Reserved
1 = Ready
2 = Starting
3 = Running
4 = Stopping
5 = Not ready (restart delay, restart
temperature check, run simulation)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
5
1 = Warning
6
0 = Uninitialised
1 = Initialised
7
Local/Remote
0 = Local control
1 = Remote control
8
Reserved
9
0 = Negative phase sequence
1 = Positive phase sequence
10 to 15
Reserved