USER MANUAL
4
Modbus TCP Interface (710-14812-00D)
To remove the interface:
1.
Remove control power and mains supply from the soft
starter.
2.
Disconnect all external wiring from the interface.
3.
Fully pull out the top and bottom retaining clips on the
interface. [A]
4.
Pull the interface away from the soft starter.
03550.
C
A
3.2
Soft Starter Connection
The device is powered from the soft starter.
CSX: For the Modbus TCP Interface to accept fieldbus commands, a link must be fitted
across terminals A1-02 on the soft starter.
The Modbus TCP Interface is not suitable for use with CSX starters using
380/440 VAC control voltage.
EMX3 and MV: Input links are required across the stop and reset inputs if the soft
starter is being operated in Remote mode. In Local mode, links are not required.
NOTE
EMX3 and MV: Control via the fieldbus communication network is always
enabled in local control mode, and can be enabled or disabled in remote
control mode (parameter 6R
Comms in Remote
). Refer to the soft starter user
manual for parameter details.
CSX
EMX3 or MV
1
4
6
9
8
.A
1
3
2
1
Soft starter
1
Soft starter (remote mode)
A1, 02: Stop input
C31, C32: Stop input
C41, C42: Reset input
2
Modbus TCP Interface
2
Modbus TCP Interface
3
RJ45 Ethernet ports
3
RJ45 Ethernet ports
1
4
6
9
9
.A
1
3
2