USER MANUAL 

Modbus TCP Interface (710-14812-00D) 

 

13 

Register  Description 

Bits 

Details 

30254 

Starter state 

0 to 4 

0 = 

Reserved

 

1 = Ready 
2 = Starting 
3 = Running 
4 = Stopping 
5 = Not ready (restart delay, restart 
temperature check, run simulation) 
6 = Tripped 
7 = Programming mode 
8 = Jog forward 
9 = Jog reverse   

 

 

1 = Warning 

 

 

0 = Uninitialised 
1 = Initialised 

 

 

0 = Local control 
1 = Remote control 

 

 

Reserved

 

 

 

0 = Negative phase sequence 
1 = Positive phase sequence 

 

 

10 to 15  Refer to 

Trip Codes

 on page 19. 

30255 

Current 

0 to 13  Average rms current across all three phases 

 

 

14 to 15 

Reserved

 

30256 

Current 

0 to 9 

Current (% motor FLC) 

 

 

10 to 15 

Reserved

 

30257 

Motor 
temperature 

0 to 7 

Motor 1 thermal model (%) 

 

8 to 15  Motor 2 thermal model (%) 

30258 

Power 

0 to 11  Power 

 

 

12 to 13  Power scale 

0 = Multiply power by 10 to get W 
1 = Multiply power by 100 to get W 
2 = Power (kW) 
3 = Multiply power by 10 to get kW 

 

 

14 to 15 

Reserved

 

30259 

% Power factor  0 to 7 

100% = power factor of 1 

 

 

8 to 15 

Reserved

 

30260 

Voltage 

0 to 13  Average rms voltage across all three phases 

(medium voltage products only) 

 

 

14 to 15 

Reserved

 

30261 

Current 

0 to 13  Phase 1 current (rms) 

 

 

14 to 15 

Reserved

 

Содержание EMX3-0053B

Страница 1: ...t starters CSX 24 VAC VDC and 110 240 VAC control voltage The Modbus TCP Interface is not suitable for use with CSX starters using 380 440 VAC control voltage EMX3 all models MV all models Disclaimer The examples and diagrams in this manual are included solely for illustrative purposes The information contained in this manual is subject to change at any time and without prior notice In no event wi...

Страница 2: ...rical installation and the system design to avoid hazards either in normal operation or in the event of equipment malfunction System design installation commissioning and maintenance must be carried out by personnel who have the necessary training and experience They must read this safety information and this guide carefully 2 2 Product Design The Modbus TCP Interface allows the soft starter to co...

Страница 3: ...ontrol power and mains supply from the soft starter 2 Fully pull out the top and bottom retaining clips on the interface A 3 Line up the interface with the comms port slot B 4 Push in the top and bottom retaining clips to secure the interface to the starter C 5 Connect Ethernet Port 1 or Port 2 on the Modbus TCP Interface to the network 6 Apply control power to the soft starter A B C 10178 C MV Pl...

Страница 4: ...TCP Interface is not suitable for use with CSX starters using 380 440 VAC control voltage EMX3 and MV Input links are required across the stop and reset inputs if the soft starter is being operated in Remote mode In Local mode links are not required NOTE EMX3 and MV Control via the fieldbus communication network is always enabled in local control mode and can be enabled or disabled in remote contr...

Страница 5: ...by 200 mm If the Ethernet cable must cross motor or mains cables the crossing should be at an angle of 90 3 4 Network Establishment The controller must establish communications directly with each device before the device can participate in the network 3 5 Addressing Each device in a network is addressed using a MAC address and an IP address The device can be assigned a static IP address during con...

Страница 6: ...eb server will only accept connections from within the same subnet domain Changes made via the on board web server are stored permanently in the device If the subnet domain of the device is different from the controller or if the IP address has been changed and is no longer known use the Ethernet Device Configuration Tool to scan the network and identify the device Changes made via the Ethernet De...

Страница 7: ...net Device Configuration Tool to connect to the device if you do not know the IP address or if the subnet mask of the web server does not match To configure settings using the Ethernet Device Configuration Tool the device must be installed in a soft starter control power must be available and the device and PC must both be connected to the Ethernet network The Ethernet Device Configuration Tool ca...

Страница 8: ...d 6 Feedback LEDs 1 2 T X R X 2 T X R X 1 L i n k 2 L i n k 1 E r r o r S t a t u s P o w e r 14702 B LED name LED Status Description Power Off Device is not powered up On Device is receiving power Error Off No error Flashing System error On Communication error Status Off Not ready Slow flash Ready but not configured Fast flash Configured and waiting for communication On Communication has been est...

Страница 9: ...2 Ensuring Safe and Successful Control Data written to the device will remain in its registers until the data is overwritten or the device is reinitialised The device will not transfer successive duplicate commands to the soft starter If the soft starter is started via fieldbus communications but stopped via the keypad or a remote input an identical start command cannot be used to restart the star...

Страница 10: ...in the Modbus Protocol Specification The mode of operation is determined by the values of bit 15 in register 40001 Standard Mode set Bit 15 1 Bits 0 7 of register 40001 are used for command Legacy Mode set Bit 15 0 The remaining bits of register 40001 are reserved Examples 10000000 00000001 start the motor Standard Mode 10000000 00000000 stop the motor Standard Mode 00000000 xxxxxxxx switch to Leg...

Страница 11: ...rved 40008 Reserved 40009 2 Parameter management single multiple read or multiple write 0 to 15 Manage soft starter programmable parameters 1 Ensure that the programmable input is not set to Motor Set Select before using this function 2 Refer to the relevant soft starter literature for a complete parameter list The first product parameter is always allocated to register 40009 The last product para...

Страница 12: ...ramming mode 8 Jog forward 9 Jog reverse 4 1 Positive phase sequence only valid if bit 6 1 5 1 Current exceeds FLC 6 0 Uninitialised 1 Initialised 7 to 15 Reserved 30241 Trip code 0 to 7 Refer to Trip Codes on page 19 8 to 15 Reserved 30242 Motor current 0 to 7 Average 3 phase motor current A 8 to 15 Reserved 30243 Motor temperature 0 to 7 Motor 1 thermal model 8 to 15 Reserved 30244 30249 Reserve...

Страница 13: ... Codes on page 19 30255 Current 0 to 13 Average rms current across all three phases 14 to 15 Reserved 30256 Current 0 to 9 Current motor FLC 10 to 15 Reserved 30257 Motor temperature 0 to 7 Motor 1 thermal model 8 to 15 Motor 2 thermal model 30258 Power 0 to 11 Power 12 to 13 Power scale 0 Multiply power by 10 to get W 1 Multiply power by 100 to get W 2 Power kW 3 Multiply power by 10 to get kW 14...

Страница 14: ...served 30265 Voltage 0 to 13 Phase 2 voltage rms medium voltage products only 14 to 15 Reserved 30266 Voltage 0 to 13 Phase 3 voltage rms medium voltage products only 14 to 15 Reserved 30267 Parameter list version number 0 to 7 Parameter list minor revision 8 to 15 Parameter list major version 30268 Digital input state 0 to 15 For all inputs 0 open 1 closed shorted 0 Start 1 Stop 2 Reset 3 Input A...

Страница 15: ...Details 40001 Reserved 0 to 14 Reserved 15 Must be zero 40002 Command single write 0 to 2 To send a command to the starter write the required value 1 Start 2 Stop 3 Reset 4 Quick stop coast to stop 5 Forced communication trip 6 Start using Parameter Set 1 7 Start using Parameter Set 2 3 to 15 Reserved 40003 Starter state 0 to 3 1 Ready 2 Starting 3 Running 4 Stopping including braking 5 Restart de...

Страница 16: ...parameters 8 to 15 Reserved 40600 Version 0 to 5 Binary protocol version 6 to 8 Parameter list version number 9 to 15 Product type code 4 CSX 6 EMX3 11 MV 40601 Reserved 40602 Reserved 40603 Reserved 40604 Starter state 0 to 4 0 Reserved 1 Ready 2 Starting 3 Running 4 Stopping 5 Not ready restart delay restart temperature check run simulation 6 Tripped 7 Programming mode 8 Jog forward 9 Jog revers...

Страница 17: ...wer factor of 1 8 to 15 Reserved 40610 Voltage 0 to 13 Average rms voltage across all three phases medium voltage products only 14 to 15 Reserved 40611 Current 0 to 13 Phase 1 current rms 14 to 15 Reserved 40612 Current 0 to 13 Phase 2 current rms 14 to 15 Reserved 40613 Current 0 to 13 Phase 3 current rms 14 to 15 Reserved 40614 Voltage 0 to 13 Phase 1 voltage rms medium voltage products only 14 ...

Страница 18: ...iterature for a complete parameter list The first product parameter is always allocated to register 40009 The last product parameter is allocated to register 40XXX where XXX 008 plus total number of available parameters in the product The Modbus TCP protocol limits read write operations to a maximum of 123 registers at one time The registers must be consecutive These registers support multiple wri...

Страница 19: ...ption function not available in inside delta 15 Starter communication between device and soft starter 16 Network communication between device and network 17 Internal fault x where x is the fault code detailed in the table below 201 Ground fault 23 Parameter out of range 24 Input B trip 25 Bypass fail bypass contactor 26 L1 phase loss 27 L2 phase loss 28 L3 phase loss 29 L1 T1 shorted 30 L2 T2 shor...

Страница 20: ...on card is fitted 2 For EMX3 time overcurrent protection is only available on internally bypassed models Internal Fault X The table below details the internal fault code associated with trip code 17 Internal fault Message displayed on the keypad 70 72 Current Read Err Lx 73 ATTENTION Remove Mains Volts 74 76 Motor Connection Tx 77 79 Firing Fail Px 80 82 VZC Fail Px 83 Low Control Volts 84 98 Inte...

Страница 21: ... which in turn connects to another device until all devices are connected 14695 A NOTE The device has an integrated switch to allow data to pass through in line topology The device must be receiving control power from the soft starter for the switch to operate NOTE If the connection between two devices is interrupted the controller cannot communicate with devices after the interruption point NOTE ...

Страница 22: ... port of the interface connects to another device which in turn connects to another device until all devices are connected The final device connects back to the switch The device supports beacon based ring node configuration 14696 A NOTE The network switch must support loss of line detection 9 4 Combined Topologies A single network can include both star and line components 14700 A ...

Страница 23: ...nections Soft starter 6 way pin assembly Contacts Gold flash Network RJ45 Settings IP address Automatically assigned configurable Device name Automatically assigned configurable Network Link speed 10 Mbps 100 Mbps auto detect Full duplex Auto crossover Power Consumption steady state maximum 35 mA 24 VDC Reverse polarity protected Galvanically isolated Certification RCM IEC 60947 4 2 CE EN 60947 4 ...

Страница 24: ...USER MANUAL 24 Modbus TCP Interface 710 14812 00D ...

Отзывы: