Line
Function
Setting range or display
Setting
increment
Basic setting
8760
I
Circulation pump, circuit 2
Off, On
Not
concerned
8770
I
Room temperature 2
0... 50 °C
--
Ambient temperature setpoint 2
20°C
8773
U
Flow temperature 2
0... 140 °C
--
Flow temperature setpoint 2
--
8820
I
DHW pump
Off, On
Off
8821
I
DHW electrical resistance
Off, On
Off
8830
U
DHW (domestic hot water) temperature
0... 140 °C
--
DHW temperature setpoint
50 °C
8840
S
DHW pump operating times
0 2730 h
--
8841
S
DHW pump start-ups counter
0 199999
--
8842
S
DHW electric operating times
0 2730 h
--
8843
S
DHW electric start-ups counter
0 65535
--
8900
U
Swimming pool temperature
0... 140 °C
--
Swimming pool temperature setpoint
22 °C
8950
I
Common flow temperature
0... 140 °C
--
Common flow temperature setpoint
--
8957
I
Common flow setpoint, refrigeration
0... 140 °C
--
8980
I
Not used
8981
I
Not used
9031
I
Relay output QX1
Off, On
On
9032
I
Relay output QX2
Off, On
On
9033
I
Relay output QX3
Off, On
Off
9034
I
Relay output QX4
Off, On
Off
9035
I
Relay output QX5
Off, On
Off
9050
I
Relay output QX21 module 1
Off, On
Not
concerned
9051
I
Relay output QX22 module 1
Off, On
Not
concerned
9052
I
Relay output QX23 module 1
Off, On
Not
concerned
9053
I
Relay output QX21 module 2
Off, On
Not
concerned
9054
I
Relay output QX22 module 2
Off, On
Not
concerned
9055
I
Relay output QX23 module 2
Off, On
Not
concerned
9071
I
Relay output QX31
Off, On
Off
9072
I
Relay output QX32
Off, On
Off
9073
I
Relay output QX33
Off, On
Off
9074
I
Relay output QX34
Off, On
Off
9075
I
Relay output QX35
Off, On
Off
Installation and commissioning instructions "1485 - EN"
Heat pump alféa hybrid duo gas
- 60 -