Line
Function
Setting range or display
Setting
increment
Basic setting
Additional generator (Boiler connection)
3692
S
With DHW charging
Locked, Substitute,
Complement, Instantly
Substitute
- DHW Instantly :
When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute :
If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700
S
Release under outside temperature (
)
-50... 50 °C
1 °C
2 °C
3701
S
Release above outside temperature
-50... 50 °C
1 °C
--
3705
S
Time delay on stopping
0 120 min
1 min
0
3720
S
Release integr boiler connection
0... 500 °Cmin
1 °Cmin
100 °Cmin
3723
S
Locking time
1 120 min
1 min
--
Domestic hot water (DHW)
5024
S
Differential
0... 20 °C
1 °C
7 °C
5030
S
Limitation on load duration
10 600 min
10 min
90 min
5055
S
Recooling temp
10... 95 °C
1 °C
65 °C
5057
S
Recooling collector
Off, Summer, Always
Summer
5061
S
Release of electrical resistance
24h / day, Release of DHW,
Programme 4 / DHW
Release of
DHW
5093
S
Not used
Installation configuration
5700
I
Pre-settings
1,2,3,... 10
1
10
For all installation configurations, the preset is 10
5710
S
Heating circuit 1
Off, On
Off
For a simple installation (1 radiator circuit only) =
Stop
With 2 circuit kit option (2 circuits or 1 underfloor heating circuit) =
On
5711
S
Heating circuit 2
Off, On
On
5715
S
DHW controlling element Q3
No charging request,
Charging pump,
Diverting valve
Diverting
valve
5731
S
Type el imm heater flow
1 : 3-stage, 2 : 2-stage excluding,
3 : 2-stage complementary,
4 : Modulating UX
3 :
2-stage
complementary
5806
I
Contact type input EX1
Normally-closed contact (NC)
Normally-opened contact (NO)
NO
5981
S
Contact type input EX2
Normally-closed contact (NC)
Normally-opened contact (NO)
NC
5983
S
Contact type input EX3
Normally-closed contact (NC)
Normally-opened contact (NO)
NO
5985
S
Not used
6098
S
Outside temperature sensor correction
-3... 3 °C
0,1 °C
0 °C
6100
S
Installation frost-free mode
On, Off
On
6120
S
Re-initialise parameters
No, Yes
No
6205
S
Reset parameters
No, Yes
No
6220
S
Software version (RVS)
0 99
--
Installation and commissioning instructions "1485 - EN"
Heat pump alféa hybrid duo gas
- 56 -