2.5
Installing the hydraulic module
2.5.1 Room where to install
• The room where the appliance operates must respect
the regulations in force.
This equipment may not be installed in a bathroom
or a shower room.
The atmospheric conditions in the room must not be
humid; humidity is damaging for electrical appliances.
If the ground is humid or soft, use a base of sufficient
height
• To facilitate the servicing operations and permit access to
the various parts, it is recommended that sufficient space
be left all around the hydraulic module (
).
• If necessary, install the hydraulic module on anti-
vibration posts or any other resilient material to limit
the sound level caused by vibration.
• Room-sealed ( turbo) pipe
(C13, C33)
As the appliance is leakproof, no specific precautions
are required concerning ventilation of the premises.
•
With Separate pipe adaptor
(C53)
Configuration possible only in boiler room.
• With chimney adaptor
(B23, B23P)
The appliance must be installed in a suitable and
well ventilated room. The room must have a fresh
air inlet (
A
) with a free non-blockable cross section
of at least 50 cm
2
located in the lower part and a
used air outlet (
B
) with a free non-blockable cross
section of at least 100 cm
2
positioned in the upper
part and opening directly outdoors (see
).
The air renewal volume must be at least (P(kW) x 2) m
3
/h,
i e 48 m
3
/h.
The warranty on the heater will not cover any installation
of the appliance in a chlorine rich atmosphere
(hairdressers, launderette, etc.) or any other corrosive
vapours.
• Be careful of the presence of inflammable gas close
to the heat pump when it is installed, especially
when brazing is required. The appliances are not
antiexplosion and must therefore not be installed in an
explosive atmosphere.
-
To avoid condensation inside the condenser, remove
the refrigerant circuit caps
only when building the
refrigerant connections
-
If the refrigerant connection only occurs at the end of
the installation, be sure that the refrigerant circuit caps*
remain in place and tight throughout the installation
duration.
* (hydraulic unit side and outdoor unit side)
-
After every intervention on the refrigeration circuit and
before final connection, take care to replace the plugs
in order to avoid any pollution from the refrigeration
circuit (The sealing with tape is prohibited).
figure 15 -
Minimum installation clearances around the
hydraulic module and gaps to the combustible partitions
300 mm
B
A
1000 mm
125 mm
1800 mm
Installation and commissioning instructions "1485 - EN"
Heat pump alféa hybrid duo gas
- 18 -