127
126
The appliance can be connected in the following ways:
1 phase connection (1 1N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c.
Install connecting bridges between connection points 1-2 and 4-5.
Your group must be protected by a fuse of at least 32 A. The connecting
power cable must have a minimum core cross section of 6 mm
2
.
2 lives with 2 neutrals connection (2 2N a.c. 230 V / 50 Hz):
The voltage between live and neutral is 230 V a.c. There may be a
voltage of 0 V between the phases if they are connected to the same
phase in the meter cupboard but also 400 V if they are connected to 2
different phases. Your groups must be fused with at least 16 A (2x).
The connecting power cable must have a minimum core cross section of
2,5 mm
2
.
INSTALLATION
electrical connection
INSTALLATION
For the connection, use an approved cable, in accordance with the
regulations. The cable casing should be of rubber.
There is a label on the underside of the appliance with the wiring
diagrams. The connection terminals are accessible once you have opened
the junction box on the underneath. The junction box cover can be
opened with a screwdriver.
If you want to make a fixed connection, make sure that a multi-polar
switch with a contact separation of at least 3 mm is fitted in the supply
line.
Power setting table
electrical connection
Type of hob
HI6171T
Induction
x
Electrical connection
230 V - 50 Hz
x
Maximum power cooking zones
Front left
3100 W
Rear left
2000 W
Rear right
2800 W
Front right
2800 W
Power connection
L1
3100 W
L2
2800 W
Total power connection
5900 W
generator right
generator left
generator right
generator left