18
DCB-05V2 Gate Controller
Owner Installation Instructions
Symptom
Possible cause
Remedy
Gate will not operate
Mains power not switched on.
Switch on mains power.
Control Box not wired correctly
Check all wiring from motor and microswitches to
the control board are sound (Section 5)
Opener motor is disengaged
Check that the motor is engaged for automatic
operation
Gate is obstructed.
Remove obstruction.
The opener is in “Vacation Mode”
Turn off “Vacation Mode”(Appendix C Menu 7.4).
Gate starts to close but
automatically reverses to
open position
Adverse weather conditions (wind
or cold) causing gate to stiffen and
become tight in the tracks.
Increase force margin setting (Section 9.4)
Possible obstruction in the
doorway.
Remove obstruction
Gate operates from control
box but not from transmitter
Transmitter code not stored in
memory.
Code transmitter in to openers memory.
(Section 10.1)
Transmitter does not contain
TrioCode
™128 Technology
Check the transmitter. It should have grey buttons
and the model number should display V2. Contact
dealer for support if otherwise.
Flat battery in transmitter
Replace battery (Section 15)
Antenna behind structure (gate or
fence) or not in line of sight
Ensure Antenna is in line of sight (Section 4.2)
Gate does not close with
transmitter
Safety Beam not working properly.
Make sure Safety Beams are operational. and no
dirt is on the lens.
Gate will not close fully.
Gate limit positions need to be
reset.
Reset limits positions.
Gate obstructed and reverses
Clear obstruction or adjust force margin
(Section 9.3)
Door will not open fully.
Gate limit positions need to be
reset.
Reset limits positions. (Section 8)
Gate obstructed.
Clear obstruction or adjust force margin
(Section 9.3)
Auto-Close not working
Safety Beam not installed.
Install Safety Beam. (Refer to Safety Beam Manual)
Safety Beam or wiring faulty.
Repair Safety Beam or replace wiring.
Safety Beam not aligned correctly.
Re-align optics.
Safety Beam is obstructed.
Remove obstruction from path of Safety Beams.
Gate obstructed when closing.
Remove obstruction.
Auto-Close time not set.
Set Auto-Close times (Section 13.3).
Auto-Close mode not set
Set Auto-Close mode. (Section 13.2)
18. Troubleshooting
Parameter
Min
Max
Default
Step
Unit
Menu
Section
Menu 1 - Code Transmitter
STORING TRANSMITTERS
0.0
511
1
10.1
Menu 2 - Current Trips
Parameter (Limit Switch)
M1 MARGIN
Sets obstruction detection margin for M1
0.0
5.0
0.7
0.1
AMPS
2.1
9.3
M2 MARGIN
Sets obstruction detection margin for M2
0.0
5.0
0.7
0.1
AMPS
2.2
9.3
SETTLE TIME disable the obstruction detection in the start of the
cycle
0.1
2.0
1.0
0.1
SEC
2.3
Parameter (AMP Limits
STOP DETECT MARGIN AMPS
0.0
5.0
1.5
0.1
AMPS
2.4
Appendix H
Motor 1 Open Limit AMPS Sets Motor 1 open limit detection current
0.0
8.0
AUTO
0.1
AMPS
2.5
Appendix H
Motor 1 Close Limit AMPS Sets Motor 1 close limit detection current
0.0
8.0
AUTO
0.1
AMPS
2.6
Appendix H
Motor 2 Open Limit AMPS Sets Motor 2 open limit detection current
0.0
8.0
AUTO
0.1
AMPS
2.7
Appendix H
Motor 2 Close Limit AMPS Sets Motor 2 close limit detection current
0.0
8.0
AUTO
0.1
AMPS
2.8
Appendix H
Maximum startup amps sets maximum permitted starting current of
motors
0.0
6.0
5.0
0.1
AMPS
2.9
Appendix H
Parameter (timed travel)
Cutout AMPS maximum motor current permitted after startup
0.0
10.0
10.0
0.1
AMPS
2.10
Appendix H
Menu 3 - Auto Close
STD AUTO-CLOSE TIME
Sets and enables the standard Auto-Close time
0.0
300.0
0.0
1.0
Sec
3.1
13.1
SAFETY BEAM AUTO-CLOSE TIME Sets and enables the SB
triggered Auto-Close time
0.0
60.0
0.0
1.0
Sec
3.2
13.2
PEDESTRIAN AUTO-CLOSE TIME Sets and enables the Pedestrian
Auto-Close time
0.0
60.0
0.0
1.0
Sec
3.3
13.3
SAFETY BEAM PEDESTRIAN AUTO-CLOSE TIME Sets and
enables the SB Pedestrian Auto-Close time
0.0
60.0
0.0
1.0
Sec
3.4
13.3
AUTO-CLOSE AFTER CLOSE OBSTRUCTION
Enables Auto-Close feature after close obstructions
Off
On
Off
3.5
13.4
AUTO-CLOSE AFTER OPEN OBSTRUCTION
Enables Auto-Close feature after open obstructions
Off
On
Off
3.6
13.4
AUTOCLOSE AFTER POWERUP
Enables autoclose feature after powerup
Off
On
Off
3.7
13.4
Menu 4 - Lock Times
OPEN LOCK TIME Set the time the lock is activated for on open
cycles
0.0
Hold
0.5
0.1
Sec
4.1
14.1
CLOSE LOCK TIME Set the time the lock is activated for on close
cycles
0.0
Hold
0.5
0.1
Sec
4.2
14.1
PRE-OPEN LOCK TIME Time the lock is activated for prior to
opening
0.0
25.5
0.0
0.1
Sec
4.3
14.1
PRE-CLOSE LOCK TIME Time the lock is activated for prior to
closing
0.0
25.5
0.0
0.1
Sec
4.4
14.1