D6021/D6031 Double Unit Series
(Push Side) Power Operator
Factory Pre-Wiring of Connections and Incoming Wiring
Controller Error Codes
Error Code
Description
Short Circuit
A short was sensed on the motor outputs
Temperature Trip
Power module reached 200°F or greater (too much load in too hot ambient
condition)
Over Voltage
Line Voltage has reached 145VAC or greater
Under Voltage
Line Voltage has dropped below 80VAC
Aux 1 Stuck
Activation device connected to Aux 1 is sending constant signal
Aux 2 Stuck
Activation device connected to Aux 2 is sending constant signal
Aux 3 Stuck
Activation device connected to Aux 3 is sending constant signal
Comm Error
No communication between top and bottom controller boards. Boards not
functioning properly
Presence Detect
Device connected to Presence Detect and was activated
Drive Disabled
Selector mode switch on end cap closest to latch is in “OFF” position
To connect wiring:
For Incoming 120VAC and 24VDC for accessories
1. For 20 - 10 AWG wire
2.
Strip end of wire 1/4 inch
3. Insert wire into appropriate position as shown
and use flat head screw driver to secure
For Low Voltage / Dry Contacts on Inverter
1. For 24 - 16AWG wire
2.
Strip end of wire 3/8 inch
3.
Use flat blade screw driver to push down on
white button above desired location, insert
wire, release button. Pull on wire to confirm
installed properly.