Check list– Testing before initial operation
EN
Checking and documenting the permanent release
1 Activate permanent release.
Identifier
Yes
No
Is the door released? (test manually)
Can the door be opened without using considerable effort?
Do the green LEDs illuminate?
2 Press the emergency button.
Identifier
Yes
No
Are the yellow and green LEDs on the terminal illuminated?
Does the integrated acoustic alarm sound?
Checking and documenting the hazard warning system
This function test is not necessary if no hazard alarm system, for example fire
alarm system, is connected.
1 Activate the locking system.
Identifier
Yes
No
Do the red LEDs light up?
Is the door securely locked? (test manually)
2 Open the closed current loop of the hazard alarm system.
Identifier
Yes
No
Is the door released without a delay?
Can the door be opened without using considerable
effort?
Are the yellow and green LEDs on the terminal illuminated?
Does the integrated acoustic alarm sound?
Optional