77
Performance Data
ACK-E-2009
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition:
23°C DB, 15°C WB
Outdoor Condition:
37°C DB
Indoor DB
˚
C Indoor WB
˚
C
Outdoor DB,
˚
C
35
37
40
TC (kW)
SC (kW)
TC (kW) SC (kW) TC (kW) SC (kW)
........
........
........
........
........
........
23
15
......................
3.295
3.859
x
y
4.828
3.41
Total capacity, TC
Interpolation Method:
⇒
40º C – 35º C
=
4.828kW – 3.295kW
40º C – 37º C
4.828kW –
χ
⇒
x = 3.908kW
Sensible capacity, SC
Interpolation Method:
⇒
40º C – 35º C
=
3.41kW – 3.859kW
40º C – 37º C
3.41kW – y
⇒
y = 3.679kW