25
Application Information
ACK-E-2009
(3) Refrigerant Piping
Maximum Piping Length and Maximum Number of Bends
When the pipe length becomes too long, both the capacity and reliability drop. As the number of bends
increases, system piping resistance to the refrigerant
fl
ow increases, thus lowering the cooling capacity,
and as the result the compressor may become defective. Always choose the shortest path and follow the
recommendation as tabulated below:
Model
Indoor
20E/ER
25E/ER
28E/ER
40E/ER
50E/ER
Outdoor
20C/CR
25C/CR
28C/CR
35/40C/CR
50C/CR
Maximum Length, m
15
15
15
45
45
Maximum Elevation, m
8
8
8
25
25
Maximum No. of Bends
10
10
10
10
10
Piping Sizes (Flare Connection Type)
Piping sizes are as follows:
R22
Model
ALC 20C/CR
ALC 25C/CR
Liquid (mm/in)
6.35 / 1/4
9.52 / 3/8
Suction (mm/in)
15.88 / 5/8
15.88 / 5/8
Model
ALC 28C/CR
ALC 35/ 40C/CR
ALC 50C/CR
Liquid (mm/in)
9.52 / 3/8
9.52 / 3/8
9.52 / 3/8
Suction (mm/in)
15.88 / 5/8
19.05 / 3/4
19.05 / 3/4
R410A
Model
A5LC 20C/CR
A5LC 25C/CR
Liquid (mm/in)
6.35 / 1/4
6.35 / 1/4
Suction (mm/in)
12.70 / 1/2
15.88 / 5/8
Model
A5LC 28C/CR
A5LC 35C/CR
A5LC 40C/CR
A5LC 50C/CR
Liquid (mm/in)
9.52 / 3/8
9.52 / 3/8
9.52 / 3/8
9.52 / 3/8
Suction (mm/in)
15.88 / 5/8
15.88 / 5/8
15.88 / 5/8
15.88 / 5/8
05_Application Information_A.ind25 25
05_Application Information_A.ind25 25
4/6/2009 3:32:56 PM
4/6/2009 3:32:56 PM
Содержание A5CK 20E
Страница 115: ...113 Wiring Diagram ACK E 2009 08024 105059 Indoor Unit Outdoor Unit Model ACK A5CK 40E Model ALC A5LC 35 40C 1 Phase...
Страница 116: ...114 ACK E 2009 Wiring Diagram 08024 105061 Indoor Unit Outdoor Unit Model ACK A5CK 40 50E Model ALC A5LC 40 50C 3 Phase...
Страница 118: ...116 ACK E 2009 Wiring Diagram 08024 105063 Indoor Unit Outdoor Unit Model ACK 40ER Model ALC 35 40CR 1 Phase...
Страница 119: ...117 Wiring Diagram ACK E 2009 08024 105064 Indoor Unit Outdoor Unit Model ACK 40 50ER Model ALC 35 40CR 3 Phase ALC 50CR...
Страница 120: ...118 ACK E 2009 Wiring Diagram 08024 105065 Indoor Unit Outdoor Unit Model A5CK 40ER Model A5LC 35CR 1 Phase...