127
Troubleshooting
ACK-E-2009
ii ) Diagnosis of Refrigerant Circuit / Application
There might be some causes where the unit starts running but does not perform satisfactorily, i.e. insuf
fi
cient
cooling. Judgement could be made by measuring temperature difference of indoor unit’s intake and discharge
air as well as running current.
: Faulty
: Check
: Cause
: Remedy
Insuf
fi
cient cooling
Indoor / outdoor coil dirty
(clogged)
Indoor air
fi
lter dirty
Restriction e.g. at strainer,
capillary,
fi
lter dryer, etc.
Restricted
Compressor
Refrigerant
circuit
High cooling
load
Air
circulation
Clean the coil
Clean the
fi
lter
Fan motor malfunction
Change or repair the motor
Obstruction at air inlet /
outlet of indoor / outdoor
unit
Remove the obstruction
Excessive heat source.
e.g. electric kettle
Remove or reduce heat source
Room overcrowded with
people
Reduce number of people in the room
Windows / doors wide
open
Close the windows / doors
Refrigerant short charge
or refrigerant leakage
Add refrigerant. Repair leakage if detected
Repair clogging or replace faulty components
Less or no compression
(Low running current)
Replace compressor
Satisfactory operation with temperature difference of air
intake & discharge of indoor unit 8°C to 13°C. *
( * value is for reference only )
13_Troubleshooting_A.indd 127
13_Troubleshooting_A.indd 127
4/6/2009 11:17:12 AM
4/6/2009 11:17:12 AM
Содержание A5CK 20E
Страница 115: ...113 Wiring Diagram ACK E 2009 08024 105059 Indoor Unit Outdoor Unit Model ACK A5CK 40E Model ALC A5LC 35 40C 1 Phase...
Страница 116: ...114 ACK E 2009 Wiring Diagram 08024 105061 Indoor Unit Outdoor Unit Model ACK A5CK 40 50E Model ALC A5LC 40 50C 3 Phase...
Страница 118: ...116 ACK E 2009 Wiring Diagram 08024 105063 Indoor Unit Outdoor Unit Model ACK 40ER Model ALC 35 40CR 1 Phase...
Страница 119: ...117 Wiring Diagram ACK E 2009 08024 105064 Indoor Unit Outdoor Unit Model ACK 40 50ER Model ALC 35 40CR 3 Phase ALC 50CR...
Страница 120: ...118 ACK E 2009 Wiring Diagram 08024 105065 Indoor Unit Outdoor Unit Model A5CK 40ER Model A5LC 35CR 1 Phase...
Страница 121: ...119 Wiring Diagram ACK E 2009 08024 105066 Indoor Unit Outdoor Unit Model A5CK 40ER Model A5LC 40CR 1 Phase...