Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 43
]
Pr7 Group - Program 7
no. Param.
Description
Dec.
Point
Values
Default
344
P7.F
Program 7 - Action at power up
0
nonE
Programmer not used;
S.uP.d Start at power up with a first step in stand-by;
S.uP.S Start at power up;
u.diG
Start at Run command detection only;
u.dG.d Start at Run command with a first step in stand-by.
nonE
345
P7.u
Program 7 - Time unit of the soaks
2
hh.nn
Hours and minutes;
nn.SS Minutes and seconds.
hh.nn
346
P7.E
Program 7 - Instrument behaviour at the
end of the program execution
0
cnt Continue;
SPAt
Go to the set point selected by A.SP;
St.by
Go to stand-by mode.
A.SP
347
P7.nE
Program 7 - Number of executions
0
1... 99 times/inF indefinitely
348
P7.Et
Program 7 - Time of the end program
indication
2
0.00 (oFF)/0.01... 99.59 nn.ss/inF (steady ON)
oFF
349
P7.S1
Program 7 - Set point of the first soak
dP
From SPLL to SPHL
0
350
P7.G1
Program 7 - Gradient of the first ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
351
P7.t1
Program 7 - Time of the 1
st
soak
2
0.00... 99.59 Time unit of the soaks
0.10
352
P7.b1
Program 7 - Wait band of the 1
st
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
353
P7.E1
Program 7 - Events of the 1
st
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
354
P7.S2
Program 7 - Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
355
P7.G2
Program 7 - Gradient of the 2
nd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
356
P7.t2
Program 7 - Time of the 2
nd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
357
P7.b2
Program 7 - Wait band of the 2
nd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
358
P7.E2
Program 7 - Events of the 2
nd
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
359
P7.S3
Program 7 - Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
360
P7.G3
Program 7 - Gradient of the 3
rd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
361
P7.t3
Program 7 - Time of the 3
rd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
362
P7.b3
Program 7 - Wait band of the 3
rd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
363
P7.E3
Program 7 - Events of the 3
rd
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
364
P7.S4
Program 7 - Set point of the 4
th
soak
dP
OFF or from SPLL to SPHL
0
365
P7.G4
Program 7 - Gradient of the 4
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
366
P7.t4
Program 7 - Time of the 4
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
367
P7.b4
Program 7 - Wait band of the 4
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
368
P7.E4
Program 7 - Events of the 4
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
369
P7.S5
Program 7 - Set point of the 5
th
soak
dP
OFF or from SPLL to SPHL
0
370
P7.G5
Program 7 - Gradient of the 5
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
371
P7.t5
Program 7 - Time of the 5
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
372
P7.b5
Program 7 - Wait band of the 5
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
373
P7.E5
Program 7 - Events of the 5
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
374
P7.S6
Program 7 - Set point of the 6
th
soak
dP
OFF or from SPLL to SPHL
0
345
P7.G6
Program 7 - Gradient of the 6
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
376
P7.t6
Program 7 - Time of the 6
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
377
P7.b6
Program 7 - Wait band of the 6
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
378
P7.E6
Program 7 - Events of the 6
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
379
P7.c3
Program 7 - Continues on program 8
0
no Program 7 is ended;
YES Program 7 will continue on program 8.