Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 10
[19] o2F - Out 2 function
Available:
When the instrument has out 2 option.
Range:
nonE
Output not used. With this setting the
status of this output can be driven directly
from serial link;
H.rEG Heating output;
c.rEG Cooling output;
AL
Alarm output;
P.End Program end indicator;
P.HLd Program hold indicator;
P. uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure
indicator;
St.By
Stand By status indicator;
diF1
Repeates the digital input 1 status;
diF2
Repeates the digital input 2 status;
on
Out2 always ON;
riSP
Inspection request.
For other details see [14] O1F parameter.
m
When a servomotor control is desired,
both
Out2
and
Out3
are to be selected as Heating or Cooling
(
o2F
=
o3F
=
HrEG
or
o2F
=
o3F
=
crEG
).
Parameter
[56] cont
must be set as
3pt
.
[20] o2.AL - Alarms linked up with Out 2
Available:
When [19] o2F = AL.
Range:
0... 63 with the following rule:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 loop break alarm;
+16 Sensor break (burn out);
+32 Overload on Out 4 (short circuit on OP4).
For more details see [17] o1.AL parameter.
[21] o2Ac - Out 2 action
Available:
When [19] o2F is different from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with revers LED indication;
rEU.r
Reverse action with reverse LED indication.
For more details see [18] o1.Ac parameter.
[22] o3F - Out 3 function
Available:
When the instrument has out 3 option.
Range:
nonE
Output not used. With this setting the status
of this output can be driven directly from
serial link;
H.rEG Heating output;
c.rEG Cooling output;
AL
Alarm output;
P.End Program end indicator;
P.HLd Program hold indicator;
P. uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure
indicator;
St.By
Stand By status indicator;
diF1
Repeates the digital input 1 status;
diF2
Repeates the digital input 2 status;
on
Out3 always ON;
riSP
Inspection request.
m
When a servomotor control is desired,
both
Out2
and
Out3
are to be selected as Heating or Cooling
(
o2F
=
o3F
=
HrEG
or
o2F
=
o3F
=
crEG
).
Parameter
[56] cont
must be set as
3pt
.
For other details see [14] O1F parameter.
[23] o3.AL - Alarms linked up with Out 3
Available:
When [21] o3F = AL.
Range:
0... 63 with the following rule:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Loop break alarm;
+16 Sensor break (burn out);
+32 Overload on Out 4 (short circuit on OP 4).
For more details see [17] o1.AL parameter.
[24] o3Ac - Out 3 action
Available:
When [20] o3F is different from
nonE
.
Range:
dir
Direct action;
rEU
Reverse action;
dir.r
Direct action with revers LED indication;
rEU.r
Reverse action with reverse LED indication.
For more details see [18] o1.Ac parameter.
[25] o4F - Out 4 function
Available:
When the [9] io4.F = Out4.
Range:
nonE
Output not used. With this setting the status
of this output can be driven directly from
serial link;
H.rEG Heating output;
c.rEG Cooling output;
AL
Alarm output;
P.End Program end indicator;
P.HLd Program hold indicator;
P. uit
Program wait indicator;
P.run
Program run indicator;
P.Et1
Program Event 1;
P.Et2
Program Event 2;
or.bo
Out-of-range or burn out indicator;
P.FAL
Power failure indicator;
bo.PF Out-of-range, Burnout and Power failure
indicator;
St.By
Stand By status indicator;
diF1
Repeates the digital input 1 status;
diF2
Repeates the digital input 2 status;
on
Out4 always ON;
riSP
Inspection request.
For other details see [14] O1F parameter.
[26] o4.AL - Alarms linked up with Out 4
Available:
When [24] o4F = AL.
Range:
0... 63 with the following rule:
+1 Alarm 1;
+2 Alarm 2;
+4 Alarm 3;
+8 Loop break alarm;
+16 Sensor break (burn out);
+32 Overload on Out 4 (short circuit on OP4).
For more details see [17] o1.AL parameter.