AL3 group - Alarm 3 parameters
no. Param.
Description
Dec.
Point
Values
Default
44
AL3t
Alarm 3 type
0
nonE Alarm not used;
LoAb Absolute low alarm;
HiAb Absolute high alarm;
LHAo Absolute band alarm, alarm ON outside the band;
LHAi Absolute band alarm, alarm ON inside the band;
SE.br Sensor Break;
LodE Deviation low alarm (relative);
HidE Deviation high alarm (relative);
LHdo Relative band alarm, alarm ON outside the band;
LHdi Relative band alarm, alarm ON inside the band.
nonE
45
Ab3
Alarm 3 function
0
0... 15:
+1 Not active at power up;
+2 Latched alarm (manual reset);
+4 Acknowledgeable alarm;
+8 Relative alarm not active at set point change.
0
46
AL3L
- For High and low alarms, AL3L is the low
limit of the AL3 threshold;
- For band alarm, it is low alarm threshold
dp
From -1999 to AL3H (E.U.)
-1999
47
AL3H
- For High and low alarms, AL3H is the
high limit of the AL3 threshold;
- For band alarm, it is high alarm threshold
dp
From AL3L to 9999 (E.U.)
9999
48
AL3
AL3 threshold
dp
From AL3L to AL3H (E.U.)
0
49
HAL3
AL3 hysteresis
dp
1... 9999 (E.U.)
1
50
AL3d
AL3 delay
0
0 (oFF)/1... 9999 (s)
oFF
51
AL3o
Alarm 3 enabling during Stand-by mode and
out of range conditions
0
0 Alarm 2 disabled during Stand by and out of range;
1 Alarm 2 enabled in stand by mode;
2 Alarm 3 enabled in out of range condition;
3 Alarm 3 enabled in stand by mode and in over-
range condition.
0
]
LBA group - Loop Break Alarm Parameters
no. Param.
Description
Dec.
Point
Values
Default
52
LbAt
LBA time
0
0 (oFF)/1... 9999 (s)
oFF
53
LbSt
Delta measure used by LBA during Soft start dP
0 (oFF)/1... 9999 (E.U.)
10
54
LbAS
Delta measure used by LBA
dP
1... 9999 (E.U.)
20
55
LbcA
Condition for LBA enabling
0
uP
Active when Pout = 100%;
dn
Active when Pout = -100%;
both
Active in both cases.
both
]
rEG group - Control Parameters
no. Param.
Description
Dec.
Point
Values
Default
56
cont
Control type
0
Pid
PID (heat and/or);
On.FA ON/OFF asymmetric hysteresis;
On.FS ON/OFF symmetric hysteresis;
nr
Heat/Cool ON/OFF control with neutral zone;
3Pt
Servomotor control (available only when
Output 2
and
Output 3
have been ordered as “
M
”).
Pid
57
Auto
Autotuning selection
0
-4 Oscillating auto-tune with automatic restart at power up and
after set point change;
-3 Oscillating auto-tune with manual start;
-2 Oscillating -tune with automatic start at the first power up only;
-1 Oscillating auto-tune with automatic restart at every power up;
0 Not used;
1 Fast auto tuning with automatic restart at every power up;
2 Fast auto-tune with automatic start the first power up only;
3 FAST auto-tune with manual start;
4 FAST auto-tune with automatic restart at power up and after
set point change;
5 Evo-tune with automatic restart at every power up;
6 Evo-tune with automatic start the first power up only;
7 Evo-tune with manual start;
8 Evo-tune with automatic restart at power up and after a set
point change.
7
58
tunE
Manual start of the Autotuning
0
oFF
Not active;
on Active.
oFF