Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 30
Appendix A
]
inP GROUP - Main and auxiliary input configuration
no. Param.
Description
Dec.
Point
Values
Default
1
SEnS
Sensor selection (according to the HW)
Model C
0
J
TC J
(-50... +1000°C/-58... +1832°F);
crAL TC K
(-50... +1370°C/-58... +2498°F);
S
TC S
(-50... 1760°C/-58... +3200°F);
r
TC R
(-50... +1760°C/-58... +3200°F);
t
TC T
(-70... +400°C/-94... +752°F);
n
TC N
(-50... +1300°C/-58... +2372°F);
Ir.J
Exergen IRS J (-46... +785°C/-50... 1445°F);
Ir.cA Exergen IRS K (-46... +785°C/-50... 1445°F);
Pt1
RTD Pt 100
(-200... 850°C/-328... 1562°F);
Pt10 RTD Pt 1000 (-200... 850°C/-328... 1562°F);
0.60 0... 60 mV;
12.60 12... 60 mV;
0.20 0... 20 mA;
4.20 4... 20 mA;
0.5
0... 5 V;
1.5
1... 5 V, ;
0.10 0... 10 V;
2.10 2... 10 V.
J
Model E
J
TC J
(-50... +1000°C/-58... +1832°F);
crAL TC K
(-50... +1370°C/-58... +2498°F);
S
TC S
(-50... 1760°C/-58... +3200°F);
r
TC R
(-50... +1760°C/-58... +3200°F);
t
TC T
(-70... +400°C/-94... +752°F);
n
TC N
(-50... +1300°C/-58... +2372°F);
Ir.J
Exergen IRS J (-46... +785°C/-50... 1445°F);
Ir.cA Exergen IRS K (-46... +785°C/-50... 1445°F);
Ptc
PTC KTY81-121
(-55... 150°C/-67... 302°F);
ntc
NTC 103-AT2
(-50... 110°C/-58... 230°F);
0.60 0... 60 mV;
12.60 12... 60 mV;
0.20 0... 20 mA;
4.20 4... 20 mA;
0.5
0... 5 V;
1.5
1... 5 V;
0.10 0... 10 V;
2.10 2... 10 V.
2
dp
Decimal Point Position (linear inputs)
0
0... 3
0
Decimal Point Position (different than linear inputs)
0/1
3
SSc
Initial scale read-out for linear inputs
dp
-1999... +9999°
0
4
FSc
Full Scale Readout for linear inputs
dp
-1999... +9999°
1000
5
unit
Engineering unit
°C/°F
°C
6
Fil
Digital filter on the measured value
1
0 OFF
0.1... 20.0 s
1.0
7
inE
Sensor error used to enable the safety output
value
or
Over range;
ou
Under range;
our
Over and under range.
our
8
oPE
Safety output value (% of the output)
-100... 100
0
9
IO4.F
I/O 4 function
on
Output used as PWS for TX;
out4 Output 4 (digital output 4);
dG2c Digital input 2 driven by contact;
dG2U Digital input 2 driven by voltage.
out4
10
diF1
Digital Input 1 function
oFF Not used;
1 Alarm reset;
2 Alarm acknowledge (ACK);
3 Hold of the measured value;
4 Stand by mode;
5 Manual mode;
6 Program RUN;
7 Program Reset;
8 Program Hold;
9 Program Run/Hold;
10 Program Run/Reset;
11 Sequential SP selection;
12 SP1 - SP2 selection;
13 SP1... SP4 binary selection;
14 Digital inputs in parallel to
and
keys.
oFF
11
diF2
Digital Input 2 function
oFF
12
di.A
Digital Inputs Action
(DI2 only if configured)
0 DI1 direct action, DI2 direct action;
1 DI1 reverse action, DI2 direct action;
2 DI1 direct action, DI2 reverse action;
3 DI1 reverse action, DI2 reverse action.
0