![Ascon tecnologic KM5P Series Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/ascon-tecnologic/km5p-series/km5p-series_engineering-manual_2981539042.webp)
Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 42
]
Pr6 Group - Program 6
no. Param.
Description
Dec.
Point
Values
Default
308
P6.F
Program 6 - Action at power up
0
nonE
Programmer not used;
S.uP.d Start at power up with a first step in stand-by;
S.uP.S Start at power up;
u.diG
Start at Run command detection only;
u.dG.d Start at Run command with a first step in stand-by.
nonE
309
P6.u
Program 6 - Time unit of the soaks
2
hh.nn
Hours and minutes;
nn.SS Minutes and seconds.
hh.nn
310
P6.E
Program 6 - Instrument behaviour at the
end of the program execution
0
cnt Continue;
SPAt
Go to the set point selected by A.SP;
St.by
Go to stand-by mode.
A.SP
311
P6.nE
Program 6 - Number of executions
0
1... 99 times/inF indefinitely
312
P6.Et
Program 6 - Time of the end program
indication
2
0.00 (oFF)/0.01... 99.59 nn.ss/inF (steady ON)
oFF
313
P6.S1
Program 6 - Set point of the first soak
dP
From SPLL to SPHL
0
314
P6.G1
Program 6 - Gradient of the first ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
315
P6.t1
Program 6 - Time of the 1
st
soak
2
0.00... 99.59 Time unit of the soaks
0.10
316
P6.b1
Program 6 - Wait band of the 1
st
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
317
P6.E1
Program 6 - Events of the 1
st
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
318
P6.S2
Program 6 - Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
319
P6.G2
Program 6 - Gradient of the 2
nd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
320
P6.t2
Program 6 - Time of the 2
nd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
321
P6.b2
Program 6 - Wait band of the 2
nd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
322
P6.E2
Program 6 - Events of the 2
nd
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
323
P6.S
Program 6 - Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
324
P6.G3
Program 6 - Gradient of the 3
rd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
325
P6.t3
Program 6 - Time of the 3
rd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
326
P6.b3
Program 6 - Wait band of the 3
rd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
327
P6.E3
Program 6 - Events of the 3
rd
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
328
P6.S4
Program 6 - Set point of the 4
th
soak
dP
OFF or from SPLL to SPHL
0
329
P6.G4
Program 6 - Gradient of the 4
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
330
P6.t4
Program 6 - Time of the 4
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
331
P6.b4
Program 6 - Wait band of the 4
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
332
P6.E4
Program 6 - Events of the 4
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
333
P6.S5
Program 6 - Set point of the 5
th
soak
dP
OFF or from SPLL to SPHL
0
334
P6.G5
Program 6 - Gradient of the 5
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
335
P6.t5
Program 6 - Time of the 5
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
336
P6.b5
Program 6 - Wait band of the 5
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
337
P6.E5
Program 6 - Events of the 5
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
338
P6.S6
Program 6 - Set point of the 6
th
soak
dP
OFF or from SPLL to SPHL
0
339
P6.G6
Program 6 - Gradient of the 6
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
340
P6.t6
Program 6 - Time of the 6
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
341
P6.b6
Program 6 - Wait band of the 6
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
342
P6.E6
Program 6 - Events of the 6
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
343
P6.c3
Program 6 - Continues on program 7
0
no Program 6 is ended;
YES Program 6 will continue on program 7.