Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 37
]
Ser group - Serial link parameters
no. Param.
Description
Dec.
Point
Values
Default
98
Add
Instrument address
oFF;
1... 254.
1
99
bAud
baud rate
1200 1200 baud;
2400 2400 baud;
9600 9600 baud;
19.2 19200 baud;
38.4 38400 baud.
9600
100
trSP
Selection of the value to be
retransmitted (Master)
nonE
Retransmission not used (the instrument is a slave);
rSP
The instrument becomes a Master and retransmits the
operative set point;
PErc
The instrument become a Master and it retransmits the
power output.
nonE
]
CAl group - User calibration parameters
no. Param.
Description
Dec.
Point
Values
Default
101
AL.P
Adjust Low Point
From -1999 to (AH.P - 10) in engineering units
0
102
AL.o
Adjust Low Offset
-300... +300 (E.U.)
0
103
AH.P
Adjust High Point
From (AL.P + 10) to 9999 (E.U.)
9999
104
AH.o
Adjust High Offset
-300... +300
0
]
PRG group - Programmer function parameters
no. Param.
Description
Dec.
Point
Values
Default
126
PAGE
Active program page election
1... 2
127
Pr.n
Active program
1... 8
128
Pr.St
Active program Status
rES
Program reset;
run
Program Start;
HoLd Program Hold;
cnt
Continue (read only).
]
Pr1 Group - Program 1
no. Param.
Description
Dec.
Point
Values
Default
129
P1.F
Program 1 - Action at power up
0
nonE
Programmer not used;
S.uP.d Start at power up with a first step in stand-by;
S.uP.S Start at power up;
u.diG
Start at Run command detection only;
u.dG.d Start at Run command with a first step in stand-by.
nonE
130
P1.u
Program 1 - Time unit of the soaks
2
hh.nn
Hours and minutes;
nn.SS Minutes and seconds.
hh.nn
131
P1.E
Program 1 - Instrument behaviour at the
end of the program execution
0
cnt Continue;
SPAt
Go to the set point selected by A.SP;
St.by
Go to stand-by mode.
A.SP
132
P1.nE
Program 1 - Number of executions
0
1... 99 times/inF indefinitely
133
P1.Et
Program 1 - Time of the end program
indication
2
0.00 (oFF)/0.01... 99.59 nn.ss/inF (steady ON)
oFF
134
P1.S1
Program 1 - Set point of the first soak
dP
From SPLL to SPHL
0
135
P1.G1
Program 1 - Gradient of the first ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
136
P1.t1
Program 1 - Time of the 1
st
soak
2
0.00... 99.59 Time unit of the soaks
0.10
137
P1.b1
Program 1 - Wait band of the 1
st
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
138
P1.E1
Program 1 - Events of the 1
st
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
139
P1.S2
Program 1 - Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
140
P1.G2
Program 1 - Gradient of the 2
nd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
141
P1.t2
Program 1 - Time of the 2
nd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
142
P1.b2
Program 1 - Wait band of the 2
nd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
143
P1.E2
Program 1 - Events of the 2
nd
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
144
P1.S3
Program 1 - Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
145
P1.G3
Program 1 - Gradient of the 3
rd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
146
P1.t3
Program 1 - Time of the 3
rd
soak
2
0.00... 99.59 Time unit of the soaks
0.10