11
Indication of remote and local events on the LCD
The local control panel ID is always displayed on the LCD (see
Figure 3 on page
9).
If your control panel forms part of a fire network, the event notification include
s
the panel ID reporting the event as follows:
•
If the panel ID matches the local ID, t
hen the event relates to the local control
panel.
•
If the panel ID does not match the local ID, then the event is reported by the
remote control panel with the panel ID indicated.
Acoustic indicators
The control panel uses the following acoustic indicators to highlight system
events.
Table 6: Control panel acoustic indicators
Indication
Description
The buzzer sounds continuously
Indicates a fire alarm or a system fault
The buzzer sounds intermittently (long tone) [1]
Indicates all
other faults
The buzzer sounds intermittently (short tone) [1]
Indicates a condition
[1] A long tone is 50% ON and 50% OFF. A short tone is 25% ON and 75% OFF.
Conditions
A summary of system events logged as conditions is shown below.
Table 7: System events logged as conditions
Condition type
Description
Alert
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
Configuration device connected
A control panel configuration session is initiated via an
external device (PC, laptop, etc.)
Date and time not set
The system started but the date and time are not set
Disablements
A control panel feature or device is disabled
Event log full
The control panel event log is full
Extinguishing status [1]
Extinguishing is blocked, disabled, or has a fault
Extinguishing I/O device [1]
An extinguishing I/O device is active, being tested, is
disabled, or has a fault
Input activation
An input is activated (subject to configuration)
Loop device not configured
A loop device is detected that is not configured
Maximum conventional zones
exceeded in a network
The number of conventional zones in a fire network
exceeds the maximum allowed
Содержание 2X Series