7
Control/LED
LED colour
Description
Programmable
start/stop button and
LED
Yellow
Starts or stops the the output group associated with
the programmable button.
A steady yellow LED indicates that the output group
associated with the button is active. A flashing
yellow LED indicates that a delay is counting (the
output group is activated when the configured delay
elapses or when the delay is cancelled).
Supply Fault LED
Yellow
Indicates a power supply fault.
A flashing LED indicates a battery fault. A steady
LED indicates a mains or mains fuse fault.
Earth Fault LED
Yellow
Indicates an earth isolation fault.
Low Battery LED
Yellow
Indicates that the control panel is running on battery
power and that the remaining charge may be
insufficient to guarantee continued operation.
System Fault LED
Yellow
Indicates a cont
rol panel system failure.
Sounder Start/Stop
button and LED
Red
The LED indicates what happens when the button
is pressed:
If the LED is on (flashing or steady), pressing the
button silences the sounders.
If the LED is off, pressing the button activates t
he
sounders (if the control panel status and operating
mode allow manual activation of sounders).
The LED also indicates the status of the sounders:
•
Steady indicates that sounders are active (or
will be activated shortly)
•
Flashing indicates that a delay is counting
(sounders are activated when the configured
delay elapses or when the delay is cancelled)
•
Off indicates that the sounders are off (or will
be deactivated shortly)
To prevent the immediate silencing of sounders
when an alarm is first reported, the Sounder
Start/Stop button may be temporarily blocked when
a configured sounder delay is counting down. For
more information, see “Stopping sounders or
restarting stopped sounders” on page 21.
Depending on the size of the installation,
processing commands to start or stop sounders
may take a few seconds to travel through the
system. This is why, for example, the LED may be
steady but sounders may not initially be audible.
Panel Silence button
and LED
Yellow
Silences the buzzer.
A steady LED indicates that the buzzer has been
silenced.
Reset button and LED Yellow
Resets the control panel and clears all current
system events.
A steady LED indicates that the control panel can
be reset in the current access level.
Содержание 2X Series