8
Evacuation panel controls and indicators
The table below includes information for the additional controls and indicators for
evacuation panels.
Note:
If the evacuation panel is operating in NEN 2575 mode, only sounder
output groups can be associated with the programmable start/stop buttons.
Table 4: Evacuation panel controls and indicators
Control/LED
LED colour
Description
Confirm button
Confirms the starting or stopping of the output group
associated with a programmable button (when pressed
with the corresponding programmable button).
Confirms the starting or stopping of all output groups
associated with all programmable buttons (when
pressed with the All Output Groups Start/Stop button).
All Output Groups
Start/Stop button and
LED
Red
Starts or stops all output groups associated with the
programmable buttons (when pressed with the Confirm
button).
A steady red LED indicates that all output groups
associated with the buttons are active. A flashing red
LED indicates that a delay is counting (the output
groups are activated when the configured delay elapses
or when the delay is cancelled).
Programmable
start/stop buttons and
LEDs
Red/Yellow
Starts or stops the the output group associated with the
programmable button (when pressed with the Confirm
button).
A steady red LED indicates that the output group
associated with the button is active. A flashing red LED
indicates that a delay is counting (the output group is
activated when the configured delay elapses or when
the delay is cancelled).
A flashing yellow LED indicates a fault. A steady yellow
LED indicates a disablement or a test.
Sounder, fire routing, and fire protection indications
The control panel may be configured by your installer to have several sounder,
fire routing, or fire protection groups. As groups of a single type may not always
share the same status, the front panel indications for the corresponding group
type display the general status for all groups. In the case of conflicting status
, the
highest priority status is displayed.
Note:
For evacuation panels, indications for operations associated with the
programmable buttons use the corresponding programmable button LEDs.
The following examples illustrate this operation.
There are three sounder groups, the first in fault status, the second in delayed
status, and the third in activated status. The sounder LED indications display the
fault status of the first group, the delay status of the second group, and the
activated status of the third group.