19
Table 9: Fire routing and fire protection delay indications
Delay type
Delay indications
Fire routing
A steady Fire Routing Delay LED indicates that a delay is enabled.
A flashing Fire Routing Delay LED during a fire alarm indicates that the
configured delay is active (fire routing is activated when the configured delay
elapses or when the delay is cancelled).
The countdown for an active (counting) fire routing delay or extended fire
routing delay is also displayed on the product LCD (see Figure 3 on page 9):
•
When a fire routing delay is counting (and has not been extended), the
LCD displays FR in T1: xxx sec.
•
When an extended fire routing delay is counting (investigation time), the
LCD displays FR in T2: xxx sec.
Fire protection
A steady Fire Protection Delay LED indicates that a delay is enabled.
A flashing Fire Protection Delay LED during a fire alarm indicates that the
configured delay is active (fire protection is activated when the configured
delay elapses or when the delay is cancelled).
Note:
A fire alarm activated by a manual call point overrides any configured
delay and activates fire routing or fire protection immediately (if configured).
Manually starting evacuation sounders
See “Manually starting evacuation sounders” on page 22.
Note:
Evacuation panels only. Availability of this feature at this user level is
subject to previous configuration by your installation or maintenance contractor.
Viewing current events
To view current event information, press F1 (Show events) and then select the
event type to view.
The event types available to this user level are:
•
Alarms
•
Alerts
•
Faults
•
Conditions
Alerts are device alarms that require confirmation from another configured alarm
event before an alarm is indicated at the control panel.
Conditions include all other system events. Examples: tests and disablements in
the fire system.
Viewing support information
To view support information configured by your installation or maintenance
contractor, press F3 (Support). Your installer or maintenance contractor may
configure, for example, contact information or different messages to display in
alarm and non-alarm situations.