43
3.8 A
DJUSTING THE
H
OT
W
ATER
F
LOW
R
ATE
To adjust the hot water flow rate, it is necessary to first open the hot
water tap with the highest flow rate (normally the bath tap), adjust the
cold water inlet valve until the correct temperature rise is achieved at the
stated flow rate ( ACO 35 MFFI -
∆
T@35°C
=
13.5 l/min).
Alternatively, you can advise the customer to restrict the water flow
through each individual tap, by opening the tap and slowly closing it
until the water reaches the desired temperature.
3.9 B
ALANCING THE
C
ENTRAL
H
EATING
S
YSTEM
To balance the central heating system it is first necessary to close
all radiator valves on the system, turn on the central heating, allow
the boiler to reach operating temperature and then starting at the
radiator furthest from the boiler, open the radiator valves until the
radiator becomes hot and move to the next radiator on the circuit,
working your way back to the radiator closest to the boiler.
10. Carry out check 3.6.3, verifying the inlet pressure is correct and
the CO
2
values are as stated in Table 4D (page 41).
11. Check the gas connection for tightness.
12.
Check that the ignition operates correctly and visually check the
burner flame.
13. Check that the domestic hot water is being correctly produced
by drawing hot water.
14. Check the flow rate and/or temperature of the water, depending
on the case.
15. Check that the condensate drips without difficulty into the
discharge.
F
IG
. 3.35
F
IG
. 3.36
LPG (G31)
Consumption at Nominal Capacity(G31) kg/h 2.33
Gas Consumption after 10 Minutes* kg 0,27
* Calculated at 70% maximum output