Secondary outlet Function
E
(This parameter can be modified only with the
interface PCB connected)
With the interface PCB connected, it is possible to set the boiler
to operate with one of the following accessories, (see Section
2.12 for further information). The setting can be varied by
pushing the and keys, the following options are available:
0 0
zone valve -
factory setting -
(N
OT
U
SED IN
UK)
0 1
N
OT
U
SED
0 2
N
OT
U
SED
0 3
N
OT
U
SED
36
P
UMP
O
VERRUN
P
The pump overrun time may be adjusted (after the burner has been
turned off) by pressing the programming keys and .
The following modes are available:
0 1
1 minute of pump overrun
0 2
2 minutes of pump overrun - factory setting
0 3
3 minutes of pump overrun
0 4
4 minutes of pump overrun
.....
.............................
1 5
15 minutes of pump overrun
F
IG
. 3.17
F
IG
. 3.16
Boiler types
F
Factory setting:
00 -
ACO 35 MFFI (COMBI)
T
HIS PARAMETER MUST NEVER BE ADJUSTED
.
Maximum Central Heating temperature
5
This parameter allows the setting of the maximum temperature for
the central heating circuit. The value is factory set at 82°C and
can be adjusted as illustrated in Section 3.6.1 (parameter 5).
Minimum Central Heating temperature
4
This parameter allows the setting of the minimum temperature for
the central heating circuit. The value is factory set at 46°C and
can be adjusted as illustrated in Section 3.6.1 (parameter 4).
F
IG
. 3.15
F
IG
. 3.14