network nr
Nr MEASURED PARAMETERS
1 2 3 4 5
45 Year
X X X X X
46 Day,
Month
X X X X X
47 Hours,
Minutes
X X X X X
48 Voltage
distortion
rate
X X X X X
49 Current
distortion
rate
X X X X X
50 Samples
dots
number
X X X X X
51 Filling ratio of the saving memory (%)
X X X X X
52 UTR harmonic 2
X X X X X
53 UTR harmonic 3
X X X X X
...
X X X X X
60 UTR harmonic 10
X X X X X
61 UTR harmonic 11
X X X X X
...
X X X X X
70 UTR harmonic 20
X X X X X
71 non
used
X X X X X
72 IR harmonic 2
X X X X X
73 IR harmonic 3
X X X X X
...
X X X X X
80 IR harmonic 10
X X X X X
81 IR harmonic 11
X X X X X
...
X X X X X
90 IR
harmonic
20
X X X X X
Network 1 = single phase
Network 2 = 3-phase balanced
Network 3 = 3-phase unbalanced without neutral & without leak current ( IR+IS+IT=0 )
Network 4 = 3-phase unbalanced with neutral
Network 5 = 3-phase unbalanced without neutral, measurement of the 3 currents IR, IS, IT & In leak.
The impedance and the harmonics are calculated on the R phase.
The harmonic distortion rate is calculated like below :
Y2²+Y3²+...+Y30²
THD = 100 x
Yn is the harmonic range of the rank n
Y1
= H2²+H3²+...+H30² Hn is the % rate of the n harmonic (Hn display value)
The measured parameters are programmed on the indicators like below : (details page 21)
Standard parameters :
Parameter Nr display unit decimal point position
Max. current and average power on N minutes :
Parameter Nr N minutes (10, 15mn...) display unit decimal point position
Analog DC inputs:
Parameter Nr display down scale display full scale decimal point position