![ARDETEM PECA 30 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/ardetem/peca-30/peca-30_configuration-manual_2966112033.webp)
PECA 30 / 30 E : programming-configuration
33
ARDETEM
PROGRAMMING OF THE ANALOG OUTPUTS (CURRENT) :
This programming goes on for : - the outputs 1,2 and 3 of « AnA », « AnA.A » or « AnA.P » board type.
Example :
for an « AnA » type board in position 1, we want for the first output : 4 to 20mA for a true variation
of the simple voltage VR from 50kV to 500kV, in low security.
Choice of the board Nr 1 (in position 1)
Output choice : output 1 of the board Nr 1 validation
Capture of the measured parameter number corresponding to the
output
(see the parameters list p.13)
Scale type choice of the current output : 0/20mA, 4/20mA,
-20+20mA , -5+5mA , -10+10mA , 0 5mA , 0 10mA
Parameter scale bottom
value and unit (10 3 = KILO)
Parameter scale end
value and unit (10 3 = KILO)
Security choice in case of alarm
( LO = 0mA , HI = full scale + 10% )
Choice of the next output
See capture Nr 1 page 16
Back to the board choice
Back to the measurement
JbUS
brd.1
brd.2
Sor.1
brd.1
AnA
5
brd.1
PArA
4-20
brd.1
I mA
50.00
brd.1
P dS
10 3
brd.1
P dS
500.0
brd.1
P FS
10 3
brd.1
P FS
LO
brd.1
SECU