Doc. 97111-CA-G
PECA 30 / 30 E
6
The AC signal analyser can be fitted with one optionnal board :
3 relais outputs board or 1 relay output board
Type of contacts
:
2 outputs 2 contacts – 1output 1 contact
Switching capacity
:
5A - 250V AC
Threshold setting
:
programmable (0 to 100% of measurement range)
Switching hysteresis
:
programmable (0 to 200% of threshlod)
Response time
:
programmable (0 to 25s)
3 pulse outputs board or 1 pulse output board
Type of outputs
:
relay switching
Count rate
:
programmable (0 to 10 pulses per second)
Pulse width
:
programmable (50, 100 or 250 ms)
3 analog outputs board or 1 analog output board
Galvanic insulation
:
500V
Output signal
:
programmable : -20/20mA -10/10mA -5/5mA 0/5mA
0/10mA 0/20mA 4/20mA
Scale setting
:
programmable (0 to 100% of measurement range)
Permissible
load : <
600
Ω
(20 mA)
Output resolution
:
12 bits
Accuracy
:
<0,1% full scale for -20/20mA output (in relation to the display)
Output wave
:
+/-2,5mV on 50
Ω
load
Response time
:
30 ms
Dual output board - 3 analog / 2 relay
See 3 analog otuputs board
Type of contacts
:
2 outputs 1 contact
Switching capacity
:
2A - 125V Ac
Threshold setting
:
programmable (0 to 100% of measurement range)
Switching hysteresis
:
programmable (0 to 200% of threshlod)
Response time
:
programable (0 to 25s)
Dual output board - 3 analog / 2 pulses
See 3 analog otuputs board
Type of outputs
:
relay switching
Count rate
:
programmable (0 to 10 pulses per second)
Pulse width
:
programmable (50, 100 or 250 ms
4 logic inputs board
Input signal
:
0 / 24 V (other on request)
Impedance input
:
3,3k
Ω
/ galvanic insulation : 500v