Doc. 97111-CA-G
PECA 30 / 30 E
5
General data
Housing Polycarbonate,
black
Format
96 x 96 , DIN 43700 standard
Mounting
Rack-mounted, requires 92 x 92 cut-out
Attachment
By
brackets
Protection
IP 20 for housing - IP 40 frontal protection
Connection
On rear face
2.5mm² capacity screw-in terminals for current
Indicators
3 x +/- 10 000 count indicators, extra bright digits, 9mm high
Parameter identification
12 unit and symbol labels
Programming
By means of keys on front panel
Detailed
instructions
provided
Electrical data
Auxiliary Power Supply
Voltage
High voltage version : 90 to 270 Vac or 88 to 350 Vdc
Low voltage version : 20 to 53 Vac or 20 to 75 Vdc
Power
draw
ac
supply
: 18VA , dc supply : 8W
Inputs
Voltage
2 programmable ranges Un = 150 or 500 Vac
Current
In = 1 A or 5 A to be specified on order
Measure overload
1.5 In ; 1.2 Un
Electrical overload
permanent : 750 V , 2 In
transient 10s : 1000 V , 10 In
Power consumption
voltage : impedance inputs 1 M
Ω
, current input : < 0,2 VA
Test voltage
2 KV , 50 HZ / 1 mn
Frequency
50 / 60 Hz – 400Hz available on request
Network type
single phase, 3-phase balanced or unbalanced with or without neutral
Measurements
Number of parameters
44
Accuracy rating
0,5 for U, I and P ; 1 for energies (PECA 30 E)
Measurement method
3 currents and 3 voltages simultaneous sampling
32
bits
digital
computation
Display refreshing
3 per second
Digital filtering
5 keyboard-programmable integration levels
Energy
backed-up , reading wtih 8 digits
Cycle time
350 ms 3-phase unbalanced network,
180 ms 3-phase balanced network.
Test
conditions
Operating temperatures
0 to +55 °C conform IEC60068-2-1 and IEC60068-2-2
Storage temeratures
-25 to +70 °C conform IEC60068-2-1 and IEC60068-2-2
Operating humidity
40°C and 93% no condensation, 10 days : IEC60068-2-30
Vibrations
1,5mm
or
2g
from 10 to 150Hz conform IEC60068-2-6
Applicable standard
IEC 61000-4-2 : level 3 or 6KV contact, 8KV air
IEC 61000-4-3 : level 3 or10V/m from 80MHz to 1GHz with
Amplitude
modulation
1KHz
at
80%
IEC 61000-4-4 : supply level 4 (4KV),
Inputs
/
outputs
level
4
IEC 61000-4-6 : 10Veff from 150KHz to 80MHz
Amplitude modulation 1KHz at 80%
Generic immunity standards : IEC 61000-6-2 emissions : 61000-6-4
Test standard : EN 55011 class A
Conform
with
the
European
Directive 89/336 rev. 92/31 : CE marking
Содержание PECA 30