Name
Unit
Range
Step
Description
Secondary residual
current I0x TRMS
(Res.curr.I0x TRMS
Sec")
A
0.00…300.00 0.01
The secondary TRMS current (inc. harmonics up to 31
st
) measurement
from the secondary residual current channel I01 or I02.
Table. 5.2.1 - 17. Residual phase angle measurements.
Name
Unit
Range
Step
Description
Residual current angle
I0x
("Res.curr.angle I0x")
deg
0.00…360.00 0.01
The residual current angle measurement from the I01 or I02 current
input.
calc.I0 Pha.angle
deg
0.00…360.00 0.01
The calculated residual current angle measurement.
Table. 5.2.1 - 18. Per-unit sequence current measurements.
Name
Unit
Range
Step
Description
Positive sequence
current
× In
0.00…1250.00 0.01
The measurement (in p.u.) from the calculated positive sequence
current.
Negative sequence
current
× In
0.00…1250.00 0.01
The measurement (in p.u.) from the calculated negative sequence
current.
Zero sequence current
× In
0.00…1250.00 0.01
The measurement (in p.u.) from the calculated zero sequence
current.
Table. 5.2.1 - 19. Primary sequence current measurements.
Name
Unit
Range
Step
Description
Primary positive sequence
current
("Pri.Positivesequence
curr.")
A
0.00…1000000.00 0.01
The primary measurement from the calculated positive
sequence current.
Primary negative sequence
current
("Pri.Negative sequence
curr.")
A
0.00…1000000.00 0.01
The primary measurement from the calculated negative
sequence current.
Primary zero sequence
current
("Pri.Zero sequence curr.")
A
0.00…1000000.00 0.01
The primary measurement from the calculated zero
sequence current.
Table. 5.2.1 - 20. Secondary sequence current measurements.
Name
Unit
Range
Step
Description
Secondary positive sequence
current
("Sec.Positive sequence
curr.")
A
0.00…300.00 0.01
The secondary measurement from the calculated positive
sequence current.
Secondary negative sequence
current
("Sec.Negative sequence
curr")
A
0.00…300.00 0.01
The secondary measurement from the calculated negative
sequence current.
Secondary zero sequence
current
("Sec.Zero sequence curr.")
A
0.00…300.00 0.01
The secondary measurement from the calculated zero
sequence current.
A
AQ
Q-S255
-S255
Instruction manual
Version: 2.06
26