![Arcteq AQ-S255 Скачать руководство пользователя страница 248](http://html1.mh-extra.com/html/arcteq/aq-s255/aq-s255_instruction-manual_2964907248.webp)
Scanning rate
Activation/release delay
5 ms
5...11 ms
Settings
Pick-up threshold
Release threshold
Software settable: 16…200 V, setting step 1 V
Software settable: 10…200 V, setting step 1 V
Pick-up delay
Software settable: 0…1800 s
Drop-off delay
Software settable: 0…1800 s
Polarity
Software settable: Normally On/Normally Off
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.3.2 Digital output module
Table. 9.1.3.2 - 176. Technical data for the digital output module.
Rated values
Rated auxiliary voltage
265 V (AC/DC)
Continuous carry
5 A
Make and carry 0.5 s
Make and carry 3 s
30 A
15 A
Breaking capacity, DC (L/R = 40 ms)
at 48 VDC
at 110 VDC
at 220 VDC
1 A
0.4 A
0.2 A
Control rate
5 ms
Settings
Polarity
Software settable: Normally On/Normally Off
Terminal block connection
Terminal block
Phoenix Contact MSTB 2,5/5-ST-5,08
Solid or stranded wire
Maximum wire diameter
2.5 mm
2
9.1.3.3 Milliampere module (mA out & mA in)
Table. 9.1.3.3 - 177. Technical data for the milliampere module.
Signals
Output magnitudes
Input magnitudes
4 × mA output signal (DC)
1 × mA input signal (DC)
mA input
Range (hardware)
Range (measurement)
Inaccuracy
0...33 mA
0...24 mA
±0.1 mA
A
AQ
Q-S255
-S255
Instruction manual
Version: 2.06
246
© Arcteq Relays Ltd
IM00025
Содержание AQ-S255
Страница 1: ...AQ S255 Bay control IED Instruction manual ...
Страница 2: ......
Страница 220: ...Figure 7 4 106 Example block scheme A AQ Q S255 S255 Instruction manual Version 2 06 218 Arcteq Relays Ltd IM00025 ...
Страница 240: ...Figure 8 13 127 Device installation A AQ Q S255 S255 Instruction manual Version 2 06 238 Arcteq Relays Ltd IM00025 ...