![Arcteq AQ-S255 Скачать руководство пользователя страница 145](http://html1.mh-extra.com/html/arcteq/aq-s255/aq-s255_instruction-manual_2964907145.webp)
Table. 5.4.5 - 86. Register content.
Name
Range
Date and time
dd.mm.yyyy hh:mm:ss.mss
Event
Event name
SYNx Ref1 voltage
The reference voltage of the selected stage.
SYNx Ref2 voltage
The reference voltage of the selected stage.
SYNx Volt Cond
The voltage condition of the selected stage.
SYNx Volt status
The voltage status of the selected stage.
SYNx Vdiff
The voltage difference of the selected stage.
SYNx Vdiff cond
The set condition of the voltage difference of the selected stage.
SYNx Adiff
The angle difference of the selected stage.
SYNx Adiff cond
The set condition of the angle difference of the selected stage.
SYNx fdiff
The frequency difference of the selected stage.
SYNx fdiff cond
The set condition of the frequency difference of the selected stage.
Setting group in use
Setting group 1...8 active.
5.4.6 Milliampere output control
The milliamp current loop is the prevailing process control signal in many industries. It is an ideal
method of transferring process information because a current does not change as it travels from a
transmitter to a receiver. It is also much more simple and cost-effective.
The benefits of 4...20 mA loops:
• the dominant standard in many industries
• the simplest option to connect and configure
• uses less wiring and connections than other signals, thus greatly reducing initial setup costs
• good for travelling long distances, as current does not degrade over long connections like
voltage does
• less sensitive to background electrical noise
• detects a fault in the system incredibly easily since 4 mA is equal to 0 % output.
Milliampere (mA) outputs
AQ-200 series supports up to two (2) independent mA option cards. Each card has four (4) mA output
channels and one (1) mA input channel. If the device has an mA option card, enable mA outputs at
Control
→
Device IO
→
mA outputs. The outputs are activated in groups of two: channels 1 and 2 are
activated together, as are channels 3 and 4 (see the image below).
Figure. 5.4.6 - 71. Activating mA output channels.
A
AQ
Q-S255
-S255
Instruction manual
Version: 2.06
© Arcteq Relays Ltd
IM00025
143
Содержание AQ-S255
Страница 1: ...AQ S255 Bay control IED Instruction manual ...
Страница 2: ......
Страница 220: ...Figure 7 4 106 Example block scheme A AQ Q S255 S255 Instruction manual Version 2 06 218 Arcteq Relays Ltd IM00025 ...
Страница 240: ...Figure 8 13 127 Device installation A AQ Q S255 S255 Instruction manual Version 2 06 238 Arcteq Relays Ltd IM00025 ...