Figure. 5.4.5 - 70. Simplified function block diagram of the SYN3 function.
Measured input
The function block uses analog current measurement values. The monitored magnitude is equal
to RMS values.
Table. 5.4.5 - 81. Measurement inputs of the synchrocheck function.
Signal
Description
Time base
U
1
RMS
RMS measurement of voltage U
1
/V
5ms
U
2
RMS
RMS measurement of voltage U
2
/V
5ms
U
3
RMS
RMS measurement of voltage U
3
/V
5ms
U
4
RMS
RMS measurement of voltage U
4
/V
5ms
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.4.5 - 82. Information displayed by the function.
Name
Range
Step
Description
dV / da / df LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of SYN block.
This parameter is visible only when
Allow setting of individual LN mode is
enabled in
General menu.