Table. 5.4.4 - 78. Auto-recloser shot settings.
Setting
Range
Step
Default
SG
Description
ARx Shot x
0: Disabled
1: Enabled
-
0:
Disabled 8
Enables/disables Shot x for request ARx. If "Disabled", the
ARx request skips Shot 1 and moves on to the next
enabled shot. If "Enabled", the ARx request executes
a shot according to Shot 1 settings. This selection can be
changed via the device's setting group selection in real
time.
ARx
Shot starting
delay
0.000…1800.000s 0.005s
0.000s
8
Defines the starting delay of the shot, i.e. the minimum
time an ARx request has to be active before openign the
breaker and entering the dead time delay counting. This
setting is used only when the ARx request comes from the
function's START signal. If the function's TRIP request
starting delay in not 0.000 s, the auto-recloser is
prevented from starting. Whenever the shot is not the first
one, this setting should be set to 0.000 s. This selection
can be changed via the setting group selection in real
time.
ARx
Shot dead
time delay
0.000…1800.000s 0.005s
0.000s
8
Defines the dead time delay of the shot, i.e. the breaker's
"Open" time before the auto-recloser closes the breaker.
The time calculation starts from the breaker's "Open"
signal. This selection can be changed via the device's
setting group selection in real time.
ARx Shot
Arc or Discr.
0: Arcing
1: Discrimination
-
0:
Arcing
8
Determines what happens when a fault persists after a
dead time when the breaker is closed. Can be chosen
between arcing and discrimination behavior; the selection
depends on the application. When "Arcing" time is
selected, the auto-recloser keeps the breaker closed until
Action time is spent (also with Discrimination time). If a
new request received during the Action time calculation,
the auto-recloser locks out during the reclaim time. This
selection can be changed via the device's setting group
selection in real time.
ARx Shot
action time
0.000…1800.000s 0.005s
0.000s
8
Defines the action time for the shot after dead time and
after the breaker is closed, i.e. the maximum arcing time
or discrimination time when the reclaim time is running.
When set to 0.000 s, the "Arcing" or "Discrimination" time
is disabled in the auto-recloser scheme. This setting can
be changed via the device's setting group selection in real
time.
ARx Shot
reclaim time
0.000…1800.000s 0.0005s 0.000s
0.000s
After the dead time has elapsed and the breaker is closed
by the auto-recloser, the reclaim time starts calculating. If
the process is interrupted by a new reclosing request, the
function continues to the next shot.
A
AQ
Q-S255
-S255
Instruction manual
Version: 2.06
124
© Arcteq Relays Ltd
IM00025