Segment 0 is the Program’s starting segment and defines immediately Set-Points and Events
to be applied. It can be programmed with value “0” in the segment’s time, to skip it.
Segments 1..24 define Set-Points to be applied immediately if Ramp OFF or with ramp
evolution during segment’s time up to the settled value if Ramp ON.
Note: If the equipment is in "CHAMBER OFF" and a program is started, the control is
immediately turned ON. Likewise, it’s possible to place the equipment in "CHAMBER
OFF" during the execution of a program, causing it to be immediately terminated.
“Repeats” is the number of repetitions a Program has, that is, when reaching the segment
defined to time 0 (or at the end of segment 24) it will execute again segment 1. If Repeats
=
1, the Program will run two times (the natural time plus one repetition).
“Next” determines which option is to be applied when Program finishes. If PG-END, the
Program is completed keeping the defined Set-Points from the last segment. It can be
defined another Program to be executed in sequence or the same, which means an infinitive
execution of that Program. In Programs in sequence execution, the first Program’s next
segment is segment 1.
Содержание FITOCLIMA 2500 HP
Страница 1: ...USER S MANUAL READ AND KEEP THIS INSTRUCTIONS ORIGINAL MANUAL EN ...
Страница 3: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 3 ...
Страница 13: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 13 Top view ...
Страница 14: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 14 Side view ...
Страница 15: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 15 3D view ...
Страница 20: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 20 Humidifiers Allows humidifying air inside the chamber ...
Страница 39: ...FITOCLIMA 2500 HP Mod MI 271 EN R00 23 10 2015 39 4 4 Set values configuration ...