FITOCLIMA 2500 HP
Mod. MI 271 EN / R00 23-10-2015
-46-
4.7
Program structure
A program consists of segments, each with different length and setpoints.
Segment 0: Program’s starting segment. When starting the Program, Air Temperature and
Relative Humidity Set-Points are put in this segment with the defined value, as well as
Radiation Intensity, CO2 level and Event’s Status. Segment Time is the duration the
segment takes in minute. Segment 0 is usually used as a start or stabilisation segment.
Segment 1..24: In segments 1 to 24, putting to 0 the segment’s duration time allows to
define that segment as the last of the Program. The Controller’s Set-Points will keep the
defined value in the last segment.
It’s also possible to defined if the Set-Points’ evolution is in a ramp (Ramp ON) or by direct
Set-Points (Ramp OFF), defining the number of repeats of the Program (Repeats) and the
possibility to run another sequence Program (Next Program).