CONDENSATION BOILER
AQUAKOND AKY
37
code HC0048.01GB ed.B-1406
AKY
Parameters of CPU-SMART board Version 7.00.xx
PARAMETER AKY032 AKY034 AKY050 AKY070
DESCRIPTION
Control of circulator outlet - Only standard series with electronic circulator
H11
1
0=output disabled;1=Y1 analog output enabled (PWM2);
2=Y2 analog output enabled (0÷10Vdc)
H12
V
4.0
Y2 minimum output voltage: 0÷10
H13
V
10.0
Y2 maximum output voltage: 0÷10
H14
%
80
Min value (PWM2): 0÷100
H15
%
100
Max value (PWM2): 0÷100
H16
2
2= modulation of circulator in proportion to FAN (do not change)
H17
1
0=PWM outlet (Y1) or 0/10V (Y2) - "direct” logic
0=PWM outlet (Y1) or 0/10V (Y2) - “reverse” logic
NTC2 control - not used
S2
0
0=NTC2 disabled; 1=NTC2 enabled
ST2
°C
5.0
NTC2 set point: -10÷90
P2
°C
2.0
ST2 hysteresis 0÷40
XD2
40
Neutral zone, proportional modulation band divided by 100: 4 ÷100
TN2
sec
5
Integration time: 1÷255
Antifreeze control - Active with D8=1
STA
°C
2.0
Antifreeze set point: -10÷+20
PA
°C
1.0
Antifreeze set point hysteresis: 0÷10
Flue temperature control - Active with D5=1
H41
°C
5
Flue temperature (NTC3); neutral band from 1÷50
H42
sec
5
Flue control cycle execution time (15=30secondi): 0÷255
H43
°C
95
Flue temperature at max output (Tmax with PT%=100): 0÷140
H44
°C
85
Flue temperature at medium output (Tmed with PT%=50): 0÷140
H45
°C
75
Flue temperature at minimum output (Tmin with PT%=0): 0÷140
H46
0
Running temperature of flue: 0=Modulation only - 1= Burner OFF
TH3
°C
103
Higher temperature limit (autoreset if NTC3<TH3): 0÷140
Control of Hydraulic Circuit Pressure
S5
3
Enabling B2 output for pressure sensor: 0=Disabled; 1=Enabled as ON/
OFF input; 2=Enabled as analog input without autoreset - Lock F83;
3=Enabled as analog input with autoreset - Lock F83
ST5
bar
0.60
B2 set point: 0÷9.99
P5
bar
0.30
ST5 hysteresis: 0÷9.99
XA5
V
1.18
Minimum voltage input signal from B2 pressure sensor: 0÷9.99
XB5
V
2.72
Minimum voltage input signal from B2 pressure sensor: 0÷9.99
YA5
bar
0.10
Pressure corresponding to minimum voltage of B2 sensor input
YB5
bar
2.90
Pressure corresponding to max input voltage of sensor
TH5
V
2.50
Higher pressure limit for F82 lock enabling: 0÷9.99
Water flow control in hydraulic circuit
S6
4
Enabling B3 flow sensor output: 0=disabled
1=Enabled as ON/OFF input without autoreset - Lock F85
2=Enabled as ON/OFF input with autoreset - Lock F85
3=Enabled as impulse input without autoreset - Locks F85 and F86
4=Enabled as impulse input with autoreset - Locks F85 and F86
ST6
Dal/h
56
56
70
80
Flow meter set point - in l/h (x10)
P6
5
ST6 hysteresis: - in l/h (x10)
XA6
Hz
14
Minimum frequency input signal from B3 pressure sensor: 0÷999
XB6
Hz
229
Maximum frequency input signal from B3 pressure sensor: 0÷999
YA6
l/h
29
Flow rate corresponding to minimum frequency of B3 sensor input
YB6
l/h
500
Flow rate corresponding to maximum frequency of B3 sensor input
TR6
sec
2
Delay in reporting F85/F86 locks (1=1 sec): 0÷250. In start-up phase, a
value of b15 is used.
Содержание AQUAKOND AKY
Страница 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Страница 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Страница 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Страница 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...