CONDENSATION BOILER
AQUAKOND AKY
36
code HC0048.01GB ed.B-1406
AKY
7.
MODULATION BOARD PARAMETERS
The table below reports all accepted values for parameters in CPU-PLUS board for each model of boiler.
Parameters of CPU-SMART board Version 7.00.xx
PARAMETER AKY032 AKY034 AKY050 AKY070
DESCRIPTION
d0
2
Flame modulation: 2=NTC1; 5=0÷10Vdc; 7=Modbus (SmartControl &
PID)
d1
2
Type of appliance: 0=heater; 2=boiler; 5=PCH
d2
1
Remote lock outlet (Q1): 0=disabled; 1=enabled
d3
sec
1
Circulator delay ON (RL1): 0÷255
d4
sec
60
Burner delay OFF (RL1): 0÷255 (1=5 sec 60=300 sec)
d5
1
Flue control enabled (NTC3): 0=disabled; 1=enabled
d6
sec
15
Interval between turning off and on (OFF timer) 0÷255
d7
0
Lock counter reset: 0÷1
d8
0
0
1
1
Boiler antifreeze enabled (NTC1): 0=disabled; 1=enabled
d9
0
Shutters enabled: 0=disabled; Do not change
b1
rpm
150
145
147
135
Min value motor revs (PWM1): 90÷999 (1=10 RPM)
b2
rpm
720
555
660
680
Max value motor revs (PWM1): 90÷999 (1=10 RPM)
b3
rpm
420
260
385
445
Start-up value of motor revs (PWM1): 90÷999 (1=10 RPM)
b4
2
Divider of HALL signal: 2÷3
b5
rpm
50
F3x lock; # revs x10 (50=500 rpm): 0÷300
b6
sec
20
F3x lock; error holding time before F3x lock is issued: 0÷255
b7
sec
0
Pre-washing time at max power: 0÷255
b8
sec
5
Duration of flame stabilization (start-up) 0÷255
b9
sec
15
Furnace post-washing time (FAN ON) 0÷255
b10
%
5
Increase of motor revs in % every b11 sec: 1÷100
b11
sec
2
Time range for increase of motor revs: 1÷100
b12
%
30
% of FAN motor modulation in antifreeze mode: 30÷100
b13
pwm
65
Integral coefficient (ki_pwm) to calculate PWM1- (exA36):0÷249
b14
pem
45
Proportional coefficient (kp_pwm) to calculate PWM1- (exA37):0÷249
b15
sec
60
Time for flux control at start-up 0÷255
Control for NTC1 modulation sensor with D0=2; Limit if D0=5 or 7
S1
1
NTC1 sensor enabling: 0=disabled; 1=enabled
ST1
°C
72 (75)
NTC1 set point: -10÷90 (72 for standard models - 75 for 00X0 models)
SP1
°C
4
Hysteresis SP1: 0÷10
XD1
%
40
Proportional band (4 to 100)
TN1
sec
5
Integral time: 1÷255
AC1
1
0=modulation only; 1=ON/OFF if D0=5 or 7, 0/10V modulation or
MODBUS
TH1
°C
82
Higher temperature limit for F51 lock enabling: 10÷95
autoreset if NTC1<TH1-15°C
0/10 Vdc Control - D0=5
H51
0
Enabled only with D0=5 (0/10V) 0=modulation only; 1=modulation and
ON/OFF
H52
V
0.5
OFF voltage, burner turns off if H51=1: 0÷10
H53
V
0.5
Voltage delta for burner ON
H54
sec
5
Lower input holding time: 0÷255
H55
sec
5
Higher input holding time: 0÷255
Содержание AQUAKOND AKY
Страница 2: ...CONDENSATION BOILER AQUAKOND AKY 2 code HC0048 01GB ed B 1406 AKY ...
Страница 4: ...CONDENSATION BOILER AQUAKOND AKY 4 code HC0048 01GB ed B 1406 AKY 3 7 Approval Certificate ...
Страница 5: ...CONDENSATION BOILER AQUAKOND AKY 5 code HC0048 01GB ed B 1406 AKY ...
Страница 44: ...CONDENSATION BOILER AQUAKOND AKY 44 code HC0048 01GB ed B 1406 AKY ...