47
code HG0141.00GB ed.A-2008
LRP - RAPID PRO and LK - KONDENSA
LRP and LK WARM AIR HEATER
7.3. C
onfiguring with LCD Display
The parameters can be changed only if they have been enabled
by entering the password from
Abi
menu.
The modification is also possible with a modbus address of the
board equal to Ø.
Abi (enabling change of setpoint and parameters)
The
Abi
menu has the following functions:
•
enables the change of heater setpoints under
Set
menu;
the password is one (1);
•
enables the change of parameters under
Par
menu; this
password is used by CATs and is indicated in the table of
Paragraph 5.6 "Modulation PCB Parameters".
Once the password is enabled, if no key is pressed for 10 minutes,
the programme automatically returns to the machine status.
Move using the menu arrows, select the parameter or setpoint
to be displayed with ENTER, change the parameter by pressing
the arrow keys until the desired value, then press and hold
ENTER
for at least 3 seconds; the display flashes to indicate
that the value has been stored.
Setpoint Menu
For the meaning and the default values please refer to the pa-
rameter table of Paragraph 5.6 "Modulation PCB Parameters".
H51
0/10 Vdc control;
H52
0/10 Vdc control;
H53
0/10 Vdc control;
St1
Modulation temperature;
St2
Not used;
H43
Not used;
H44
Not used;
H45
Not used;
St5
Not used;
St6
Not used;
H12
Not used;
H13
Not used;
H18
Not used.
Parameter Menu
The
Par
submenu allows the access to "b" and "d" parameters:
•
from
b1
to
b17
burner parameters;
•
from
d0
to
d10
heater operation configuration.
For the meaning and the default values please refer to the pa-
rameter table of Paragraph 5.6 "Modulation PCB Parameters".
Besides "b" and "d" parameters, the following parameters can
be changed:
S1
Modulation probe enabling;
SP1
ST1 hystereris (only if the probe is used as
temperature limit);
tH1
Maximum temperature of the modulation probe,
switches the burner off regardless of the other
conditions set;
S2
Not used;
P2
Not used;
S5
Not used;
P5
Not used;
S6
Not used;
P6
Not used;
H11
Not used;
H41
Not used
S3
Not used;
Sel
Not used;
TH3
Not used.
I/O menu - Inputs outputs
From
I/O
menu it is possible to display the values measured
by the sensors.
NTC1
Air intake temperature;
NTC2
Not used;
NTC3
Not used;
An1
0/10V input - if used;
PrH
Not used;
FLH
Not used;
rPu
no. of FAN revolutions;
Pu2
Not used;
uSA
Not used;
IOn
measures the ionization current; 0 to 100 for currents
0 to 2 microamperes, 100 above 2 microamperes.
Flt Menu (Fault)
It displays the fault event log; use the arrow keys to scroll the
list of error codes and press
ENTER
to display the historical
value of the selected fault.
The first visible value,
rst
, is used to reset the fault event log; this
operation must not be performed by the user but by the service
centre. The reset operation can be carried out by changing the
parameter to 1 and confirming it by pressing and holding
ENTER
for at least 3 seconds. After the reset,
rst
returns to 0.
The list and meanings of all faults are shown in the FAULT table
in Paragraph 5.7 "Analysis of Lockouts - Faults".