29
code HG0141.00GB ed.A-2008
LRP - RAPID PRO and LK - KONDENSA
LRP and LK WARM AIR HEATER
L
1max
L
2max
HG140.00_IM_024
L
1max
L
2max
HG140.00_IM_025
Horizontal coaxial C13 terminal
Combustion circuit watertight to the environment. The ducts go
directly through the wall.
L
max
of the pipe routing made with the Ø shown, excluding the
terminal.
The terminal consists of:
•
Adaptor from LRP or LK outlet to exhaust Ø (where nec-
essary);
•
An adaptor from LRP or LK outlet to intake Ø (where
necessary);
•
A horizontal coaxial terminal.
NOTE: The maximum length available has been split in
equal parts between the exhaust (L
1max
) and the intake
(L
2max
); the lengths between intake and exhaust can also
be split differently without exceeding the sum shown.
Ø80 pipes and bends: TC13-08-HC1
Mod. LK
020
034
045
065
080
105
L
max
[m]
30+30 30+30 15+15
5+5
-
-
Mod. LRP
018
028
035
045
055
075
102
L
max
[m]
30+30 30+30 20+20 10+10
8+8
2+2
-
Ø100 pipes and bends: TC13-10-HC2 + 2xG15835-08-10
(eccentric adaptors only for mod. LK020-065 and LRP018-075)
Mod. LK
020
034
045
065
080
105
L
max
[m]
-
-
30+30 15+15
5+5
1+1
Mod. LRP
018
028
035
045
055
075
102
L
max
[m]
-
-
30+30 30+30 30+30 10+10
2+2
Ø130 pipes and bends: TC13-13-HC5 + 2xG15815-10-13 +
2xG15810-13-45 (adaptors and bends only suitable to model
LK080-105 and LRP102)
Mod. LK
020
034
045
065
080
105
L
max
[m]
-
-
-
-
30+30 30+30
Mod. LRP
018
028
035
045
055
075
102
L
max
[m]
-
-
-
-
-
-
30+30