code HG0141.00GB ed.A-2008
LRP - RAPID PRO and LK - KONDENSA
LRP and LK WARM AIR HEATER
Parameters of CPU-SMART PCB version 7.03.xx
PARAMETER
LRP018
LRP028
LK020
LRP035
LRP045
LK034
LRP055
LK045
LRP075
LK065
LRP102
LK080
LK105
DESCRIPTION
Hydraulic circuit WATER FLOW control - NOT USED ON LRP and LK
S6
(2)
0
Flow sensor B3 output enabling: 0=disabled
1=enabled as ON/OFF input without F85 fault autoreset
2=enabled as ON/OFF input with F85 fault autoreset
3=enabled as pulsed input without F85 and F86 fault autoreset
4=enabled as pulsed input with F85 and F86 fault autoreset
ST6
(1) From
l/h
56
Flowmeter setpoint - in l/h (x10)
P6
(2)
5
ST6 hysteresis: - in l/h (x10)
XA6
(3)
Hz
14
B3 pressure probe signal input minimum frequency: 0÷999
XB6
(3)
Hz
229
B3 pressure probe signal input maximum frequency: 0÷999
YA6
(3)
l/h
29
Flow rate matching the B3 probe inlet minimum frequency
YB6
(3)
l/h
500
Flow rate matching the B3 probe inlet maximum frequency
TR6
(3) sec
2
Fault F85/F86 indication time delay (1=1second): 0÷250. During
the ignition stage, the b15 value is used.
PRESSURE control - PID parameters for ventilation of Pressostatic structures - NOT USED ON LRP and LK
kp
(3)
%
20
Proportional Gain
ki
(3)
%
5
Integral Gain
kd
(3)
%
10
Derivative Gain
li
(3)
%
100
Maximum limit of integral part
"Burner parameters - motor rpm" Table
PARAMETER
LRP018 LRP028 LRP035 LRP045 LRP055 LRP075 LRP102
DESCRIPTION
b1
rpm
540
460
427
410
417
416
346 Motor RPM MINIMUM value (PWM1): 90÷999 (1=10 rpm)- DO
NOT CHANGE
b2
rpm
815
730
703
660
690
645
618 Motor RPM MAXIMUM value (PWM1): 90÷999 (1=10RPM) -
DO NOT CHANGE
b3
rpm
340
320
315
290
355
320
317 Motor RPM START-UP value (PWM1): 90÷999 (1=10RPM) -
DO NOT CHANGE
PARAMETER
LK020
LK034
LK045
LK065
LK080
LK105
DESCRIPTION
b1
rpm
213
210
169
182
172
172 Motor RPM MINIMUM value (PWM1): 90÷999 (1=10 rpm)- DO
NOT CHANGE
b2
rpm
660
710
580
651
655
635 Motor RPM MAXIMUM value (PWM1): 90÷999 (1=10RPM) -
DO NOT CHANGE
b3
rpm
320
300
345
340
355
240 Motor RPM START-UP value (PWM1): 90÷999 (1=10RPM) -
DO NOT CHANGE
Table of "Gas-type parameters"
PARAMETER
G20
G25
G25.3
G25.1
G27
G2.350 G30 G31
DESCRIPTION
LCV
(3)
kW/m
3
9.45 8.13 8.31 8.14 7.75 6.75 12.4
Lower calorific value (Hi)