Page 22 code HG0109.12GB ed.C-1106 rev.12
APEN GROUP reserves the right to change products and documents as required.
WARM AIR HEATER SERIES RAPID
L2
L1
** using Ø80/100 male/female eccentric adapters code G15835-08-10
(to be ordered separately)
Terminals include:
• TC33-08-VC1 - Complete terminal, Ø 80/80 fittings - Centre distance 120
• TC33-10-VC2 - Complete terminal, Ø 100/100 fittings - Centre distance 140
9
8
7
This layout requires that fittings be moved from the back to the top of the
heater. For more details, see instructions below.
HG0103 C2 016
To disassemble:
1) Cut "A" covers from upper panel
2) Pull "C" flue pipe
3) Disassemble the intake joint "D"
4) Disassemble the flue joint "B"
5) Remove internal covers "E" installed one on burner casing
and the other over flue hood
How to assemble:
1) Install one "E" cover (and its seal) on the side hole of the
exchanger.
2) Install "B" flue junction on upper hole of the exchanger
3) Insert intake junction "D" on burner compartment
4) Cut to length "C" pipe and install it on "D" air junction
reaching same height as flue outlet
5) Install pre-cut covers "A" and their seals on the hole for
air intake
6) Install "E" cover without seal on back hole of the flue
Disassembling
Assembling
80/80->Ø125
100/100->Ø150
130/130->Ø200
HG0109.12_ET_012
A
B
C
D
E
HG0109.12_C2_009
C33 TYPE (ROOF)
Combustion circuit is sealed from the room. Pipes end outdoor with a
concentric terminal.
Max L1 + L2 of layout, terminal excluded
Term. Ø80/80
TC33-08-VC1
Term. Ø100/100 TC33-10-VC2
Pipes and elbows Ø80
Pipes and elbows Ø100
Model
meters
RA015
11 + 11
RA024
11 + 11
RA032
10 + 10
RA035
9 + 9
RA043
7 + 7
RA054
4,5 + 4,5
10 + 10**
REMARK: Max possible length was equally divided between intake and discharge. Different ratios
are allowed, provided the maximum value shown in the table is not exceeded.