Setup
Document No. D113-015
Page 23 of 77
Revision 1.9
Figure 3.19. – Advanced Diagnostic Builder
The builder is used to generate the command, and to define the Data Type. The following
parameters need to be defined:
Parameter
Description
Description
A user description for the advanced diagnostic parameter.
Diagnostic Type
Select
HART Pass Through
option.
HART Command
The HART command code. (decimal)
Command Length
This is the length of the data that must be sent with the command.
Result Offset
The byte offset in the response where the required parameter starts.
Data Type
The Logix tag data type required to accept the parameter.
Response Length
This is the size of the data that must be copied to the Logix Tag.
NOTE:
This is only relevant for SINT Array Data Types.
Command Data
Additional request parameters required by the HART command.
Table 3.4 – Advanced Diagnostics Build parameters
Once accepted, the full command string will be built, and the current map item will be