![Anybus CompactCom 40 EtherNet/IP Скачать руководство пользователя страница 80](http://html1.mh-extra.com/html/anybus/compactcom-40-ethernet-ip/compactcom-40-ethernet-ip_network-manual_2948758080.webp)
CIP Objects
80
Doc.Id. HMSI-27-212
Anybus CompactCom 40 EtherNet/IP
Doc.Rev. 1.5
Instance Attributes
Extended
# Name
Access Type
Value/Description
1 Energy/
Resource Type
Get
UINT
Type of energy managed by this instance
Always 0 (Generic)
2 Base Energy
Object Capabili-
ties
Get
UINT
Always 0 (Energy measured)
3 Energy Accu-
racy
Get
UINT
Specifies the accuracy of power and energy metering results, either
in 0.01 percent of reading (default) or 0.01 of other units specified in
attribute #4. If 0, unknown.
4 Energy Accu-
racy Basis
Get
UINT
Always 0 (Percent of reading)
7
a
a. Depending on whether the instance reports consumed or generated energy, either attribute #7 or attribute #8 is
required.
Consumed
Energy Odome-
ter
Get
ODOMETER
b
b. This struct data type makes it possible to represent very large values, for more information please consult the CIP
specification Volume 1 (CIP Common).
The value of the consumed energy.
Generated
Energy Odome-
ter
Get
ODOMETER
The value of the generated energy.
12 Energy Type
Specific Object
Path
Get
Struct of:
UINT (Path size)
padded EPATH
(Path)
NULL path